12.7 Indication Panel
LED POWER
TIMER QUIET
POWERFUL
AIR
SWING
Color Green Orange Orange Orange Orange
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
Auto Air Swing ON
Light OFF
Operation OFF
Timer Setting OFF
Quiet Mode OFF
Powerful Mode OFF
Auto Air Swing OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
12.8 Drain Pump Control Operation
To drain out the condensed water trapped in the drain pan in order to prevent the condensed water from
overflowing from the drain pan and leaking.
Drain Pump starts to operate 10 sec. after compressor and Indoor fan ON.
Drain Pump stop to operate 90 sec. after compressor OFF.
Drain Pump Error
Drain Pump Error occurs when:
- Within 20 minutes, the float switch is ON twice.
- Float switch is ON continuously for 2 minutes 30 seconds.
When error occurs, the timer indicator blinks and the unit stops its operation.
Summary of Contents for CS-ME9PB4EA
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 29: ...29 5 Dimensions 5 1 Indoor Unit...
Page 30: ...30 6 Refrigeration Cycle Diagram...
Page 31: ...31 7 Block Diagram...
Page 32: ...32 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 34: ...34 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 81: ...81 16 Exploded View and Replacement Parts List 16 1 Indoor Unit...