C. Anti-Fog Discharge Control
•
The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor until as shown in
the table below.
Compressor operating frequency
Operation
Time, T (min)
0
T < 30
50Hz
70Hz
30
T < 90
46Hz
64Hz
T
90
43Hz
58Hz
Model No.
CU-G95KE
CU-G125KE
Note:
•
Indoor fan is running at Me
-
or below.
•
After 420 minutes from the start of operation, the operation timer counting is restarted from “0”.
d. High Pressure Control at Minimum Frequency Control
•
When the outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to minimum of 31 Hz.
Compressor operating frequency will resume to normal when outdoor air temperature decreases to 37.8°C.