1.
Protection Control For All Operations
Model No.
CU-G95KE
CU-G125KE
I1 (A)
6.1
9.2
I2 (A)
7.3
10.8
8.2. Protection
a. Time Delay Safety Control
•
The Compressor is not restarted for 3 minutes after stop of compressor.
b. 30 Second Forced Operation
•
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control or Automatic
switch.
c. Total Running Current Control
•
When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not exceeded for
30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running current exceeds I2, the
compressor is immediately stopped for 3 minutes.
<Cooling, Soft Dry set value>
Zone A
Zone B
Model No.
CU-C95KE
CU-G125KE
CU-G95KE
CU-G125KE
I1 (A)
5.3
6.7
4.3
5.2
I2 (A)
7.3
10.8
7.3
10.8
Note: Zone A will be used 30 minutes after operation starts.
<Heating set value>
•
If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will be turned off;
TIMER LED will blink and F98 is displayed.
d. IPM (Power transistor) Prevention Control
1. Overheating Prevention Control
•
When the IPM (power transistor) temperature rises to 100 ± 10°C, the compressor stops immediately. The compressor
is restarted when the IPM (power transistor) temperature decreases to 90 ± 10°C after 3 minutes (Time Delay Safety
Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays will be turned off; TIMER LED
will blink and F96 is displayed.
42
S-G95KE CU-G95KE / CS-G125KE CU-G125KE
Summary of Contents for CS-G125KE CU-G125KE
Page 12: ...4 Dimensions 12 S G95KE CU G95KE CS G125KE CU G125KE ...
Page 13: ...13 CS G95KE CU G95KE CS G125KE CU G125KE ...
Page 14: ...5 Refrigeration Cycle Diagram 14 S G95KE CU G95KE CS G125KE CU G125KE ...
Page 15: ...6 Block Diagram 15 CS G95KE CU G95KE CS G125KE CU G125KE ...
Page 24: ... ii When indoor fan speed is lower than Medium 24 S G95KE CU G95KE CS G125KE CU G125KE ...
Page 94: ...12 Technical Data 94 S G95KE CU G95KE CS G125KE CU G125KE ...
Page 95: ...95 CS G95KE CU G95KE CS G125KE CU G125KE ...
Page 109: ...109 CS G95KE CU G95KE CS G125KE CU G125KE ...
Page 112: ...18 1 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 112 S G95KE CU G95KE CS G125KE CU G125KE ...
Page 114: ...114 S G95KE CU G95KE CS G125KE CU G125KE MACC Printed in Malaysia ...