Compressor OFF temperature = compressor ON temperature.
•
The operation frequency changes every 30 seconds.
•
When the difference of the intake air temperature and Internal setting temperature is -1.5°C or more, compressor will
operate at Fh continuously for 3 minutes and then change over to Fhmax.
•
The compressor stops when the intake air temperature reaches 1.5°C above internal setting temperature and continues for
3 minutes.
•
When the compressor stops, it will not start operation for 3 minutes. (Time Delay Safety Control)
•
When the intake air temperature decreases to the compressor ON temperature, the compressor starts immediately.
•
When the compressor stops, the outdoor fan motor stops 30 seconds later.
25
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE