[Heating]
o
According to indoor pipe temperature, automatic heating fan speed is determined as follows.
Feedback
control
o
Immediately after the fan motor started, feedback control is performed once every second.
o
During fan motor on, if fan motor feedback
≥
2550 rpm or < 50 rpm continue for 10 seconds, then fan motor
error counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then
H19 - fan motor error is detected. Operation stops and cannot on back.
12.3 Outdoor Fan Motor Operation
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops
30 seconds after compressor stops operation.
ON
ON
Compressor
OFF
ON
Fan
Speed
ON
Outdoor Fan
30 sec
OFF
12.4 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by
vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
12.4.1 Vertical
Airflow
Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the
angles as stated above. For heating mode operation, the angle of the vane depands on the indoor heat
exchanger temperature as Figure 1 below. When the air conditioner is stopped using remote control, the vane
will shift to close position.
Summary of Contents for CS-E18NKUA
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 19: ...19 10 1 2 Power Printed Circuit Board 10 1 3 Indicator and Receiver Printed Circuit Board ...
Page 20: ...20 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 21: ...21 10 2 2 Noise Filter Printed Circuit Board ...
Page 45: ...45 15 3 Error Code Table ...
Page 68: ...68 16 1 1 2 To remove discharge grille ...
Page 69: ...69 16 1 1 3 To remove control board 16 1 1 4 To remove cross flow fan and indoor fan motor ...
Page 70: ...70 ...