38
13.2.2
Cooling Overload Control
Pipe temperature limitation / restriction.
o
Detects the outdoor pipe temperature and carry out restriction / limitation below (Limit the compressor
operation frequency)
o
The compressor stops if outdoor pipe temperature exceeds 145.4°F.
o
If the compressor stops 4 times in 20 minutes, Timer LED blinks (“F95” indicated: Outdoor high pressure rise
protection)
13.2.3
Freeze Prevention Control 1
When indoor heat exchanger temperature is lower than 32°F continuously for 6 minutes, compressor will stops
operation.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 41.0°F.
At the same time, indoor fan speed will be higher than during its normal operation.
If the indoor heat exchanger temperature is higher than 55.4°F for 5 minutes, the fan speed will return to its
normal operation.
13.2.4
Freeze Prevention Control 2
Control start conditions
o
During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 50.0°F or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
13.2.5
Dew Prevention Control 1
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o
Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o
When Cooling or Dry mode is operated more than 20 minutes or more.
This control stopped if:
o
Compressor
stopped.
o
Remote control setting changed (fan speed / temperature).
o
Outdoor air temperature and indoor intake temperature changed.
Fan speed, angle of louver (vertical airflow angle) will be adjusted accordingly in this control.
1. Fan speed will be increased slowly when control is activated until predetermine value.
Compressor
frequency will be regulated accordingly.
13.2.6 Protection
Control
For Heating Operation
13.2.6.1 Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 86.0°F or above.
13.2.6.2 Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 57.2°F in order to avoid
compressor overloading.
Summary of Contents for CS-E18NKUA
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit ...
Page 11: ...11 5 2 Outdoor Unit ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 15: ...15 8 2 Outdoor Unit ...
Page 16: ...16 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 17: ...17 9 2 Outdoor Unit ...
Page 18: ...18 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 19: ...19 10 1 2 Power Printed Circuit Board 10 1 3 Indicator and Receiver Printed Circuit Board ...
Page 20: ...20 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 21: ...21 10 2 2 Noise Filter Printed Circuit Board ...
Page 45: ...45 15 3 Error Code Table ...
Page 68: ...68 16 1 1 2 To remove discharge grille ...
Page 69: ...69 16 1 1 3 To remove control board 16 1 1 4 To remove cross flow fan and indoor fan motor ...
Page 70: ...70 ...