72
Figure 9
Figure 10
16. Push the holdfast to the left and lift up the evaporator.
18. Fan motor can be removed after the
removal of cross flow fan.
Reminder: To reinstall the fan motor, adjust
the fan motor connector to 45° towards you
before fixing control board.
17. Remove the cross flow fan from the unit by
pulling it to the left and downward.
Evaporator
Reminder: To reinstall the cross flow
fan, ensure cross flow fan is in line as
shown in figure 10
Summary of Contents for CS-CE12NKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 22: ...22 10 2 Outdoor Unit ...
Page 45: ...45 15 3 Error Codes Table ...
Page 46: ...46 ...
Page 74: ...74 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU CE9NKE ...
Page 75: ...75 ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 17 1 2 CU CE12NKE ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...