
64
15.4.18 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Air short circuit at indoor unit
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty outdoor unit fan motor
Excessive
refrigerant
Clogged expansion valve or strainer
Faulty outdoor pipe temperature sensor
Faulty outdoor unit PCB
Troubleshooting
Summary of Contents for CS-CE12NKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 22: ...22 10 2 Outdoor Unit ...
Page 45: ...45 15 3 Error Codes Table ...
Page 46: ...46 ...
Page 74: ...74 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU CE9NKE ...
Page 75: ...75 ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 17 1 2 CU CE12NKE ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...