35
13. Protection
Control
13.1 Protection Control For All Operations
13.1.1 Restart
Control
(Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2 Total Running Current Control
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
If the running current does not exceed X value for 10 seconds, the frequency instructed will be increased.
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model CE9NK CE12NK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
4.54
14.76
6.20
14.76
Cooling/Soft Dry (B)
3.43
14.76
5.64
14.76
Cooling/Soft Dry (C)
3.43
14.76
5.64
14.76
Heating
5.49
14.76
8.03
14.76
The first 30 minutes of cooling operation, (A) will be applied.
13.1.3 IPM (Power transistor) Prevention Control
Overheating Prevention Control
o
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
o
If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
DC Peak Current Control
o
When electric current to IPM exceeds set value of 20.2 A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
o
If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
restart after 1 minute.
o
If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
2 minutes. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking (“F99” is indicated).
Summary of Contents for CS-CE12NKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 22: ...22 10 2 Outdoor Unit ...
Page 45: ...45 15 3 Error Codes Table ...
Page 46: ...46 ...
Page 74: ...74 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU CE9NKE ...
Page 75: ...75 ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 17 1 2 CU CE12NKE ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...