87
Floor h Swimming pool
Outdoor
Thermistor 1
Heat EXT
Thermistor 3
Thermistor 2
Buffer tank
Pump 2
Pump 3
Pump 1
Mixing valve 1
Mixing valve 2
Indoor
Floor heating 1
Swimming pool
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2
Swimming pool
T
Connect floor heating and swimming pool to 2 circuits through buffer tank as shown in figure.
Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits.
Then, install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Remove remote controller from Tank Unit and install in room where floor heating is installed. Circulation water
temperature of floor heating and swimming pool can be set independently.
Install buffer tank sensor on buffer tank.
It requires connection setting of buffer tank and ∆T temperature setting at heating operation separately. This system
requires the Optional PCB (CZ-NS5P).
Must connect swimming pool to “Zone 2”.
If it is connected to swimming pool, operation of pool will stop when “Cooling” is operated.
Note : Buffer tank thermistor must be connected to main indoor PCB only.
Swimming pool only
Thermistor
Pump
Swimming pool
Heat EX
Indoor
Outdoor
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 1 Zone system
Zone :Swimming pool
T
This is an application that connects to the swimming pool only.
Connects pool heat exchanger directly to Tank Unit without using buffer tank.
Install pool pump and pool sensor (specified by Panasonic) at secondary side of the pool heat exchanger.
Remove remote controller from Tank Unit and install in room where floor heating is installed.
Temperature of swimming pool can be set independently.
This system requires the Optional PCB (CZ-NS5P).
In this application, cooling mode cannot be selected. (not display on remote controller)