77
30
12.2.7.4 Mounting
The
Remote
Controller
For exposed type
Preparation:
Make 2 holes for screws using a driver.
Cut here with
a nipper and
remove the burr
with a file.
Mount the top case.
•
Align the claws of the top
case and then align the claws
of the bottom case.
Screw
(field supply)
Bottom case
(Back side)
Top case
(Back side)
Remote controller terminal board
Remove the coating. Approx. 6 mm
Remove the sheath. Approx. 180 mm.
Make sure the wiring connection is in the
correct direction.
Wall to which
the remote
controller is
fixed
Mount the bottom case to
the wall.
Connect the remote
control wiring
•
Arrange the wires along
the groove of the case.
For embedded type
Preparation:
Make 2 holes for screws using a driver.
Avoid the wire
being caught.
Mount the top case.
•
Align the claws of the top
case and then align the claws
of the bottom case.
Screws
(field supply)
Bottom case
(Back side)
Top case
(Back side)
Remote controller
terminal board
Remove the coating.
Approx. 6 mm
Make sure the wiring
connection is in the correct
direction.
Mount the bottom case
to the wall.
•
Pass the wire through the hole
in the centre of the bottom case.
Connect the remote
control wiring
12.2.7.5 Replace The Remote Controller
Cover
Replace the existing Remote Controller with
Remote Controller Case 4 to close the hole left
after remove the Remote Controller.
1. Refer Section “Remove The Remote Controller
From Tank Unit” for remove Remote Controller.
2. Remove the top case from the bottom case of
Remote Controller Case 4 .
Bottom
case
Top case
Insert the
driver and
slightly turn.
Flat-blade
screwdriver
3. Reverse the steps 1 to 4 of section “Remove The
Remote Controller From Tank Unit” to fix Remote
Controller Case 4 on Tank Unit.
12.2.8 Test Run
1.
Before test run, make sure below items have been
checked:-
a) Pipework are properly done.
b) Electric cable connecting work are properly
done.
c) Tank Unit is filled up with water and trapped
air is released.
d) Please turn on the power supply after filling
the tank until full.
2.
Switch ON the power supply of the Tank Unit. Set
the Tank Unit RCCB /ELCB to “ON” condition.
Then, please refer to the Operation Instruction for
operation of Remote Controller
①
.
Note:
During winter, turn on the power supply and standby the
unit for at least 15 minutes before test run.
Allow sufficient time to warm up refrigerant and prevent
wrong error code judgement.
3.
For normal operation, Water Pressure reading
should be in between 0.05 MPa and 0.3 MPa
(0.5 bar and 3 bar). If necessary, adjust the Water
Pump
④
SPEED accordingly to obtain normal
water pressure operating range. If adjust Water
Pump
④
SPEED cannot solve the problem,
contact your local authorized dealer.
4.
After test run, please clean the Magnetic Water
Filter Set
⑨
and Water Filter Set . Reinstall it
after finish cleaning.