162
Maximum length of communication cable is 50 meter.
Control content:
External Control Switch
Control Panel OFF/ON
Control Panel Power LED
System Status
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
Remocon Screen Display and Control Detail:
REMOTE
ON
N
O
N
O
ON
OFF
OFF
UNIT
OFF
OFF
OFF
ON
CONTROLLER
LED
REMOTE
CONTROLLER
SIGNA
L
EXTERNA
L
CONTROLLER
SWITCH
23
1
44
40
10:34am , Mon
18
˚
c
˚
c
˚
c
˚
c
2
Turned of by external switch.
CANCEL
When External SW connection select "YES" from remocon installer menu:
Heating or Cooling system will operate normally if the External Switch signal is ON.
Once the External Switch turn OFF, System Turn OFF (Heat pump, water pump, heater etc…)
Remocon LED remain ON or OFF according to the current operation request.
Pop up menu at remocon main screen as above screen to inform customer system stop by External Switch.
It is possible to press cancel and return to main screen to do change of operation setting while waiting the
External Switch turn ON back.
Remocon LED will always follow the latest changes from remocon.
If no action on remocon for continuous 5 minutes, the pop up screen will show again on the screen.
But once the External Switch Turn ON back, pop up screen will disappear and system can operate normally
according to the latest operation setting and request.
14.26 External Compressor Switch (Optional PCB)
External compressor switch port can have two purpose of control as below:
Heat source ON/OFF function (Dip switch Pin 3 on PCB "OFF")
Heater ON/OFF function (Dip switch Pin 3 on PCB "ON")
Heat source ON/OFF function
Purpose:
Heat pump ON/OFF function is use to turn OFF the high power consumption device (Heat pump, & Heater) when
there is energy or electric current limitation. Other optional function still can be operate under heat pump and
heater OFF condition.