138
Water Outlet Thermo Condition
Heat pump thermos OFF temperature:
1 Heat pump thermo OFF temperature = Target Water outlet tempe (1°C)
2 Water outlet temperature > heat pump thermo OFF temperature for continuously 3 minutes, heat pump OFF
but water pump continue ON.
Heat pump thermo ON temperature
1 Heat pump thermo ON temperature = water inlet during thermo OFF time + [-3°C]
2 When water outlet temperature < heat pump thermo ON temperature, heat pump ON.
Water inlet thermo protection condition
Heat pump thermo OFF temperature:
1 Water inlet temperature > [60°C/55°C] for continuously 30 seconds, heat pump OFF, water pump continue
ON.
Heat pump thermo ON temperature:
1 Heat pump thermos ON temp = water inlet temperature < [60°C/55°C].
Outdoor ambient temperature
Water inlet temperature
< -10°C
55°C
> -10°C
60°C
Thermo ON/OFF for Heat Pump in Tank Operation:
When tank temperature achieve heat pump OFF condition, refer below condition:
Conditon 1 : Tank Heater ON (Internal Tank Heater)
Heat pump will turn OFF, water pump continue ON and room heater will continue ON if tank temperature below
tank heater thermo ON condition. 3 ways valve will only switch to room side after tank temperature reach tank
heater thermo OFF condition.
Conditon 2 : Tank Heater OFF (Internal Tank Heater)
If tank temperature achieve tank thermo OFF, heat pump turn OFF, water pump turn OFF, room heater OFF and
3 ways valve switch to room side.
When tank temperature achieve heat pump ON condition, water pump ON, heat pump ON and room heater turn OFF.
Heat pump OFF condition at Tank Mode
o
Tank temperature > tank water set temperature continuously for 20 seconds after heat pump thermos OFF
due to water thermo. (Heat pump turn OFF but water pump continue ON and room heater turn ON to achieve
tank set temperature)
OR
o
Tank temperature > tank set tempe [1°C] for continuously 20 seconds. (Heat pump OFF, water pump
OFF, room heater OFF and 3 ways valve switch to room side)
Heat pump ON condition at Tank Mode
o
Tank temperature < tank water set tempe R/C setting (Tank re-heat temp) (Water pump turn ON OR
continue ON, heat pump ON and 3 ways valve switch to tank side or maintain at tank side)
Tank heater control
Internal heater only operates to tank side if Tank heater ON and backup heater is enable.
Internal heater turn ON condition:
Tank temperature < tank set temperature
AND
Heat pump thermos OFF
AND
20 minutes from previous heater off
AND
Internal tank heater selects USE from control panel.
Internal heater turn OFF condition:
Tank temperature > tank set temperature for continuously 15 seconds
OR
Heat pump thermo ON
OR
Mode change or operation is off by control panel.