WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type

shown on the rating plate. Such conversion could result in hazardous operating conditions.

!

Leak Testing

The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.

Turn on the gas shut-off valve(s) to
the water heater.

Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.

The factory connections should also be
leak tested after the water heater is placed
in operation.

High Altitude

Ratings of gas appliances are based on
sea level operation and need not be
changed for installations at elevations up
to 3,280 feet.

NOTICE: For installations above 3,280
feet, the connector on the PC board
must be replaced for High Altitude
installations.  Please contact your local
distributor, dealer, or Paloma for
replacement connector.

Pressure Testing the Gas Supply System

The water heater and its manual gas shut-
off valve must be disconnected from the
gas supply piping system during any
pressure testing of the system at
pressures in excess of 1/2 psi (14” w.c.).

The water heater must be isolated from
the gas piping system by closing the
manual gas shut-off valve during any
pressure testing of the gas supply piping at
pressures equal to or less than 
1/2 psi (14” w.c.).

Gas Supply

The supplied Manual Gas Appliance
Shutoff Valve must be installed at the gas
connection of the water heater at the time
of installation (see diagram to the left).

The branch gas supply line to the water
heater should be clean 3/4” black steel
pipe or other approved gas piping
material.

A ground joint union or ANSI design
certified semi-rigid or flexible gas
appliance connector should be installed in
the gas line close to the water heater. The
National Fuel Gas Code (NFGC)
mandates a manual gas shut-off valve: See
(NFGC) for complete instructions.

If flexible connectors are used, the
maximum length shall not exceed 36”.

If lever type gas shut offs are used, they
shall be T-Handle type.

Compound used on the threaded joints of
the gas piping must be of the type
resistant to the action of LP gas. Use
compound sparingly on male threads only. 

A sediment trap should be installed at the
bottom of the gas line.

Do not use excessive force (over 31.5 ft
lbs.) in tightening the pipe, particularly if
teflon pipe compound is used, as the unit
may be damaged.

The inlet gas pressure to the water heater
must not exceed 10.5” w.c. for natural or
14” wc for LP gas. For purposes of input
adjustment, the minimum inlet gas
pressure (with main burner on) is shown
on the water heater rating plate. If high or
low gas pressures are present, contact your
gas supplier for correction.

WARNING: Never use

an open flame to test for

gas leaks, as property

damage, personal injury, or

death  could result.

!

Manual Gas 

Appliance

Shut-off

(Supplied)

Sediment

Trap

Manual

Gas

Supply

Line

Shut-off

Valve

Union

Cap

WARNING: Install a

gas pressure regulator, in

the gas supply line, which

does not exceed the

maximum supply pressure.
DO NOT use an industrial

type gas regulator.

!

Summary of Contents for PH-28RIFSN

Page 1: ...installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also...

Page 2: ...READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is...

Page 3: ...hesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity...

Page 4: ...water temperature is recommended to reduce the risk of scald injury Contact a licensed plumber or the local plumbing authority for further information Notice The factory setting allows operating tempe...

Page 5: ...r LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to lo...

Page 6: ...ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage personal i...

Page 7: ...reduce BUT NOT eliminate the possibility of lighting the vapor of any flammable liquids which may be improperly stored or accidentally spilled The water heater should be installed as close as practica...

Page 8: ...warranty is voided when failure of the heater is due to operation in a corrosive atmosphere NOTICE The water heater should not be installed near an air supply containing halogenated hydrocarbons Inspe...

Page 9: ...water supply lines DO NOT cover the drain valves To ensure proper operation of the water heater the following water pressure guidelines should be followed Operation of the water heater requires the mi...

Page 10: ...ter damage Notice If the relief valve on the system discharges periodically a problem exists and service to the water system is required Water Supply Connections Continued Install a shutoff valve near...

Page 11: ...be installed at the gas connection of the water heater at the time of installation see diagram to the left The branch gas supply line to the water heater should be clean 3 4 black steel pipe or other...

Page 12: ...air supply for proper operation as outlined in the Venting section of this manual WARNING Use UL approved Category III Stainless Steel vent material only No other vent material is permitted WARNING Re...

Page 13: ...tructions before installation Test fit the adapter over the water heater collar before proceeding Adjust clamp as needed With an alcohol wipe clean inside surface A of adapter and outside surface of B...

Page 14: ...Not terminate vent pipe directly on brick or masonry surfaces Use a rust resistant sheet metal backing plate 2 x 2 feet behind vent See illustration Do Not locate vent terminal too close to shrubbery...

Page 15: ...board or other composite material Use 4 10x1 1 4 wood screws for plywood solid wood sheathing or members Use suitable masonry anchors when passing through solid masonry walls Reinstall the decorative...

Page 16: ...f condensate in accordance to local codes Rain Cap Storm Collar Support Clamp 1 4 per foot downward slope 2 Max Chase Requires 6 Clearance to Combustibles Firestop Firestop Roof Jack Adjustable Roof F...

Page 17: ...tween the water heater and the remote control s installation location is limited to 195 feet of wire NOTICE Only one of each type of remote controls can connect to the water heater Therefore a maximum...

Page 18: ...upwards Connect the remote control cables to the extension cable from the water heater Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in t...

Page 19: ...W BR AIR INTAKE FILTER SWITCH TRANSFORMER GND BK GND WATER FLOW SENSOR OVER HEAT LIMITER BK BLACK COLOUR CODE BR BROWN R RED W WHITE B BLUE GY GRAY GR GREEN O ORANGE Y YELLOW G Y GREEN YELLOW REMOTE...

Page 20: ...liance Shut off supplied Sediment Trap Manual Gas Supply Line Shut off Valve Union Cap Cold Water Supply Shut off Valve Check Valve Vent Adapter F PRIORITY POWER ON OFF Remote Control Power Supply Cor...

Page 21: ...er Hot and Cold Pipe Insulation Installation Gas Inlet Check Valve Inlet Pipe Cold Water Hot Water Insulate all the way to the top Insulation Blankets Insulation blankets available to the general publ...

Page 22: ...Supply Gas type matches rating plate Gas supply pressure is sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and wa...

Page 23: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Page 24: ...educing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information See page 4 for more details...

Page 25: ...ter Always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Always supervise young children or others who are incapaci...

Page 26: ...ice After inspection maintenance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and d...

Page 27: ...be turned off The water heater and piping should be drained if they might be subjected to freezing temperatures After a long shut down period the water heater s operation and controls should be check...

Page 28: ...ns for draining water out of the water heater Turn off the switch on the remote control Close the gas shut off valve s Unplug the power supply cord or disconnect breaker at least 10 seconds after step...

Page 29: ...etely The main burner goes off when incoming water volume is inadequate Check that proper power is being supplied and or water supply is adequate Fan continues to rotate after hot water faucet is clos...

Page 30: ...t water faucet once The water heater can then be used The Gas Shutoff Valve is not opened completely Gas Service has been interrupted LP Gas is running low LP models only Contact Gas Utility Company F...

Page 31: ...ls using natural or LP gas Instructions For Placing a Parts Order Address parts orders to the distributor or store from where the water heater was purchased All parts orders should include The model a...

Page 32: ...all of the other component parts warranty will be limited to one 1 year from the Effective Date WARRANTY EXCLUSIONS This Limited Warranty will not cover a Service trips to your home to teach you how t...

Page 33: ...ines that a defect exists Paloma shall furnish replacement part s in full settlement of its warranty obligations Purchasers shall be required to return at purchasers expense the defective part s to th...

Page 34: ...140 F With Main Control Dip Switch Combustion System Fan Assisted Combustion Main Burner Bunsen Type Burner Ignition Electric Continuous Sparking Ignition Electric Portion Electric Rating 120 VAC 60Hz...

Page 35: ...This page was intentionally left blank...

Page 36: ...Paloma Industries Inc 2151 Eastman Avenue Oxnard CA 93030 PRINTED IN JAPAN 31 50641...

Reviews: