10

Installing the water heater.

Relief Valve

A new pressure relief valve, complying
with the Standard for Relief Valves and
Automatic Gas Shut-Off Devices for Hot
Water Supply Systems, ANSI Z21.22,
must be installed at the hot water outlet
connection of the water heater at the
time of installation. Local codes shall
govern the installation of relief valves.

For safe operation of the water heater, be
sure that:

The pressure rating of the relief valve
must not exceed 150 psi, the maximum
working pressure of the water heater as
marked on the rating plate.

The BTUH rating of the relief valve
must equal or exceed the BTUH input
of the water heater as marked on its
rating plate.

No valve of any type should be
installed between the relief valve and
the water heater

Discharge from the relief valve should
be piped to a suitable drain to eliminate
potential water damage. Piping used
should be of a type approved for the
distribution of hot water.

Hot and cold water lines should be
insulated up to the water heater. Refer
to page 21 for details.

The discharge line must be NO
SMALLER than the outlet of the valve
and must pitch downward to allow
complete drainage (by gravity) of the
relief valve and discharge line.

The end of the discharge line should not
be threaded or concealed and should be
protected from freezing. No valve of
any type, restriction or reducer coupling
should be installed in the discharge line.

Notice

: Local codes govern the

installation of relief valves. If local codes
require that a temperature and pressure
relief valve should be installed the
manufacturer recommends a type 40XL
Watts T&P relief valve or an equivalent
model be used.

Notice

: Manual operation of relief valves

should be performed at least once a year.
Turn off the electrical power and gas
shutoff valve. Lift and release lever on the
relief valve and check the manual
operation of the relief valve. You should
take precaution to avoid contact with the
hot water coming out of the relief valve
and to prevent water damage.

Notice

: If the relief valve on the system

discharges periodically, a problem exists
and service to the water system is
required.

Water Supply Connections Continued.

Install a shutoff valve near the inlet of the
water heater for service and draining
purposes.

DO NOT use pipes with smaller diameters
than the water supply connection of the
water heater.

Before connecting the water supply pipe
to the water heater, open the shutoff valve
and clean out sand, debris, air, caulking
material, etc. inside the pipe. Connect to
the water inlet, then check water flow.
Close the shutoff valve and clean the
water filter.

Be sure to connect the water inlet and the
hot water outlet as shown on the water
heater. If reversed, the water heater will
not function.

Installation of unions or flexible copper
connections are recommended on the
HOT and COLD water lines, so that the
water heater may disconnect easily for
servicing if necessary.

Install a Check Valve between the water
heater and the water shutoff valve. (See
illustration the top left).

The following should be addressed in
regards to the HOT WATER OUTLET:

Connections between the water heater
and point(s) of use should be as short
and direct as possible.

DO NOT use lead or plastic pipe.

To conserve energy and minimize heat
loss, insulation of hot water piping is
recommended. (See Hot and Cold Pipe
Insulation Installation on page 21).

Notice

: The flow rate of hot water may

vary when more than two faucets
(appliances, fixtures, etc.) are being used
simultaneously.

Notice

: The pipes MUST be completely

drainable. If the hot water faucets are
located at a point higher than the water
heater, place a drain valve at the lowest
point (see diagram to the left).

Water Filter

Check Valve

Water Inlet

Clean the
Water Filter

Water

Nipple

Air 

Relief 
Valve

Hot 

Water 

Tap

 Drain Valve

Union

Pressure
Relief Valve 

Water

Shutoff

Valve

Cold

Water

Supply

Inlet

Hot Water

Supply

Outlet

Relief
Valve
Discharge
Line

Notice

: The above illustrates a

pressure only relief valve.  If local
codes require a combination
temperature and pressure relief
valve be installed, an extension
piece may be needed. (Refer to
page 20 for example of extension
piece for T&P relief valve
installation.)

Summary of Contents for PH-28RIFSN

Page 1: ...installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also...

Page 2: ...READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is...

Page 3: ...hesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity...

Page 4: ...water temperature is recommended to reduce the risk of scald injury Contact a licensed plumber or the local plumbing authority for further information Notice The factory setting allows operating tempe...

Page 5: ...r LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to lo...

Page 6: ...ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage personal i...

Page 7: ...reduce BUT NOT eliminate the possibility of lighting the vapor of any flammable liquids which may be improperly stored or accidentally spilled The water heater should be installed as close as practica...

Page 8: ...warranty is voided when failure of the heater is due to operation in a corrosive atmosphere NOTICE The water heater should not be installed near an air supply containing halogenated hydrocarbons Inspe...

Page 9: ...water supply lines DO NOT cover the drain valves To ensure proper operation of the water heater the following water pressure guidelines should be followed Operation of the water heater requires the mi...

Page 10: ...ter damage Notice If the relief valve on the system discharges periodically a problem exists and service to the water system is required Water Supply Connections Continued Install a shutoff valve near...

Page 11: ...be installed at the gas connection of the water heater at the time of installation see diagram to the left The branch gas supply line to the water heater should be clean 3 4 black steel pipe or other...

Page 12: ...air supply for proper operation as outlined in the Venting section of this manual WARNING Use UL approved Category III Stainless Steel vent material only No other vent material is permitted WARNING Re...

Page 13: ...tructions before installation Test fit the adapter over the water heater collar before proceeding Adjust clamp as needed With an alcohol wipe clean inside surface A of adapter and outside surface of B...

Page 14: ...Not terminate vent pipe directly on brick or masonry surfaces Use a rust resistant sheet metal backing plate 2 x 2 feet behind vent See illustration Do Not locate vent terminal too close to shrubbery...

Page 15: ...board or other composite material Use 4 10x1 1 4 wood screws for plywood solid wood sheathing or members Use suitable masonry anchors when passing through solid masonry walls Reinstall the decorative...

Page 16: ...f condensate in accordance to local codes Rain Cap Storm Collar Support Clamp 1 4 per foot downward slope 2 Max Chase Requires 6 Clearance to Combustibles Firestop Firestop Roof Jack Adjustable Roof F...

Page 17: ...tween the water heater and the remote control s installation location is limited to 195 feet of wire NOTICE Only one of each type of remote controls can connect to the water heater Therefore a maximum...

Page 18: ...upwards Connect the remote control cables to the extension cable from the water heater Place the remote control over the base plate Ensure the projections in the base plate fit into the housings in t...

Page 19: ...W BR AIR INTAKE FILTER SWITCH TRANSFORMER GND BK GND WATER FLOW SENSOR OVER HEAT LIMITER BK BLACK COLOUR CODE BR BROWN R RED W WHITE B BLUE GY GRAY GR GREEN O ORANGE Y YELLOW G Y GREEN YELLOW REMOTE...

Page 20: ...liance Shut off supplied Sediment Trap Manual Gas Supply Line Shut off Valve Union Cap Cold Water Supply Shut off Valve Check Valve Vent Adapter F PRIORITY POWER ON OFF Remote Control Power Supply Cor...

Page 21: ...er Hot and Cold Pipe Insulation Installation Gas Inlet Check Valve Inlet Pipe Cold Water Hot Water Insulate all the way to the top Insulation Blankets Insulation blankets available to the general publ...

Page 22: ...Supply Gas type matches rating plate Gas supply pressure is sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and wa...

Page 23: ...s label 2 Turn off all electric power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait...

Page 24: ...educing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information See page 4 for more details...

Page 25: ...ter Always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Always supervise young children or others who are incapaci...

Page 26: ...ice After inspection maintenance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and d...

Page 27: ...be turned off The water heater and piping should be drained if they might be subjected to freezing temperatures After a long shut down period the water heater s operation and controls should be check...

Page 28: ...ns for draining water out of the water heater Turn off the switch on the remote control Close the gas shut off valve s Unplug the power supply cord or disconnect breaker at least 10 seconds after step...

Page 29: ...etely The main burner goes off when incoming water volume is inadequate Check that proper power is being supplied and or water supply is adequate Fan continues to rotate after hot water faucet is clos...

Page 30: ...t water faucet once The water heater can then be used The Gas Shutoff Valve is not opened completely Gas Service has been interrupted LP Gas is running low LP models only Contact Gas Utility Company F...

Page 31: ...ls using natural or LP gas Instructions For Placing a Parts Order Address parts orders to the distributor or store from where the water heater was purchased All parts orders should include The model a...

Page 32: ...all of the other component parts warranty will be limited to one 1 year from the Effective Date WARRANTY EXCLUSIONS This Limited Warranty will not cover a Service trips to your home to teach you how t...

Page 33: ...ines that a defect exists Paloma shall furnish replacement part s in full settlement of its warranty obligations Purchasers shall be required to return at purchasers expense the defective part s to th...

Page 34: ...140 F With Main Control Dip Switch Combustion System Fan Assisted Combustion Main Burner Bunsen Type Burner Ignition Electric Continuous Sparking Ignition Electric Portion Electric Rating 120 VAC 60Hz...

Page 35: ...This page was intentionally left blank...

Page 36: ...Paloma Industries Inc 2151 Eastman Avenue Oxnard CA 93030 PRINTED IN JAPAN 31 50641...

Reviews: