PROGRAM EDIT MODE
This section describes the Program Edit Mode which allows program and transient definition and editing.
4.5.1 PROGRAM EDITING
To start the Program Edit Mode, from any meter display press the
PROGRAM
key, program number,
ENTER
key then
EDIT
key. The cursor will move to FORM.
PROGRAM: #1 FORM=3 COUPLING=DIRECT
FREQ=60 Va=120 Vb=120 Vc=120
WFa=1 WFb=1 WFc=1
#SEGS=0 Ilim=50 PHb=120º PHc=240º
The following may be programmed:
FORM
: Enter 1, 2, or 3 Phase output FORM.
FORM 1 enables Single phase output and is connected to the 1 Phase Output Relay. Only the
1
Φ
Output Terminal will become active. 1 Phase loads must be connected between the 1
Φ
Terminal and the “N” (neutral) Terminal.
FORM 2 enables the high range Split/Single phase output. The Power Source output is
connected to the 3 Phase Output Relay. Only
Φ
A and
Φ
B Output Terminals will become active
and are 180º out of phase. Voltages are programmed phase to phase. This may be called split
phase and can be loaded between the
Φ
A and
Φ
B Output Terminals or from either phase to “N”
(neutral) at half voltage.
FORM 3 enables 3 phase output and the Power Source is connected to the 3 Phase Output
Relay.
Φ
A,
Φ
B and
Φ
C Output Terminals will become active. Loads may be connected either
line-to-line or line-to-neutral.
COUPLING
: Select DIRECT or XFMR (transformer) coupled output by pressing the
+/-
key.
DIRECT connects the Power Amplifier directly to the Output Relay.
XFMR connects the Power Amplifier to the Output Transformers and the Transformers are then
connected to the Output Relay.
XFMR(N.NN)
: When COUPLING=XFMR is selected, you may enter the transformer ratio. The
transformer ratio for the system (see UPC STATUS, para. 4.6.3.3) must be the same as this
value before the program may be executed. Ratios above 1 are step up and ratios below 1 are
step down.
Summary of Contents for UPC-12
Page 2: ......
Page 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Page 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12 ...
Page 46: ...SECTION 4 OPERATION 34 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Page 77: ...SECTION 4 OPERATION 65 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Page 139: ...NOTES 127 NOTES ...