SECTION 5
REMOTE OPERATION
102
5.7.3 EXAMPLE OF EXECUTING A STORED PROGRAM
Step A. Address the UPC as a listener.
:PROGram:NAME 1
<eos>
Step B. Select Program 1.
NOTE:
<eos> is a LINE FEED (0Ahex, 10dec)
:PROGram:EXECute
<eos>
Step C. Execute Program.
Step D. Un-address UPC.
5.7.4 EXAMPLE OF EXECUTING A STORED PROGRAM TRANSIENT
Step A. Address the UPC as a listener.
:PROGram:NAME 1
<eos>
Step B. Select Program 1 for executing.
NOTE:
<eos> is a LINE FEED (0Ahex, 10dec).
:PROGram:EXECute
<eos>
Step C. Execute Program.
:PROGram:EXECute:TRANS
<eos>
Step D. Execute Transient.
Step E. Un-address UPC.
5.7.5 EXAMPLE OF DIRECTLY CHANGING THE OUTPUT PARAMETERS
Change Frequency and Volts for all phases then ENABLEs the OUTPUT.
Step A. Address the UPC as a listener.
:FREQuency 50
<eos> Step B. Change Frequency to 50 Hz.
:VOLTage 117
<eos>
Step C. Change Volts to 117 VAC RMS for all phases.
:OUTPut ON
<eos>
Step D. ENABLES the OUTPUT. The OUTPUT POWER switch must
be in the ON/AUTO position to allow power to be applied to the load.
Step E. Un-address UPC.
An alternative to steps B, C and D above is:
:FREQ 50; :VOLT 117; :OUT ON
<eos> This example uses all shortform keywords in one Program
Message. The OUTPUT POWER switch must be in the ON/AUTO
position to allow power to be applied to the load.
- or -
:OUTPut OFF
<eos>
Turns the output OFF.
Summary of Contents for UPC-12
Page 2: ......
Page 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Page 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12 ...
Page 46: ...SECTION 4 OPERATION 34 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Page 77: ...SECTION 4 OPERATION 65 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Page 139: ...NOTES 127 NOTES ...