68
4.6.3.1.1 PROGRAMMABLE OUTPUT IMPEDANCE SETUP MENUS (cont)
CAUTION
-
USE THIS FUNCTION WITH CARE
CARELESS OR IMPROPER USE OF THE PROGRAMMABLE OUTPUT IMPEDANCE FUNCTION
MAY RESULT IN OVER-VOLTAGE OR UNDER-VOLTAGE BEING PRESENTED TO THE LOAD,
AND MAY CAUSE DAMAGE TO THE LOAD.
REACTIVE LOADS MAY CAUSE THE OUTPUT POWER TO BECOME UNSTABLE (OSCILLATE)
AND MAY CAUSE DAMAGE TO THE LOAD IF EXCESSIVE NEGATIVE IMPEDANCE IS USED!
4.6.3.1.1.1 PROGRAMMABLE OUTPUT IMPEDANCE CALIBRATION MENU
Press
EDIT
again, while the PROG.Zo menu is displayed:
PRESS ENTER TO LOAD PROG. Zo CALIBRATION
VALUES
PRESS 0 TO RESET CALIBRATION VALUES TO
FACTORY
DEFAULTS.
Press
ENTER
to access the Prog.Zo Calibration screens to enter special calibration values for the
Prog.Zo function.
Ø
Z direct XFMR ratio Z xfmr
1 0.006 | 1.50 0.450
2 0.032 | 2.00 1.400
3 0.016 | 2.50 2.970
NOTE:
Each power source is pre-calibrated at the factory, but if re-calibration of this function is desired,
or if the RAM (memory) in the UPC has been lost or erased, use this screen to enter new calibration
values. The calibration procedure is described later.
NOTE:
Only the values pertaining to the present output FORM will be displayed.
!
Summary of Contents for UPC-1
Page 2: ......
Page 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Page 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Page 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Page 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Page 134: ...NOTES 122 NOTES ...