![Pacific Power Source UPC-1 Operation Manual Download Page 101](http://html.mh-extra.com/html/pacific-power-source/upc-1/upc-1_operation-manual_746371101.webp)
SECTION 5
REMOTE OPERATION
89
5.5.2 METERED DATA QUERIES (cont)
:MEASure:PF1?
Query: metered power factor (KW/KVA)
Φ
A.
Returns <0> to <1.0>
:MEASure:PF2?
Query: metered power factor (KW/KVA)
Φ
B.
Returns <0> to <1.0>
:MEASure:PF3?
Query: metered power factor (KW/KVA)
Φ
C
.
Returns <0> to <1.0>
:FETCh[:WAVEform]:VOLT1?
:FETCh[:WAVEform]:CURRent1?
Query: metered waveform data (line-to-neutral voltage only).
Use
:VOLT1
for
Φ
A,
:VOLT2
for
Φ
B, and
:VOLT3
for
Φ
C
volts
Use
:CURR1
for
Φ
A,
:CURR2
for
Φ
B, and
:CURR3
for
Φ
C
current
Returns a string of NR2 type numbers, comma delimited. Only a
single waveform may be queried in a command.
:MEASure:SPECTrum:VOLT1[:MAGnitude]?
(option: Harmonic Analysis and Synthesis)
[:ABSolute]?
:MEASure:SPECTrum:CURRent1[:MAGnitude]?
[ABSolute]?
Query: waveform harmonic magnitudes
Use
:VOLT1
for
Φ
A,
:VOLT2
for
Φ
B, and
:VOLT3
for
Φ
C
volts
Use
:CURR1
for
Φ
A,
:CURR2
for
Φ
B, and
:CURR3
for
Φ
C
current
Returns a data set of 51, NR2 type numbers, comma delimited. The
1
st
element is the magnitude of the fundamental, for reference. The 2
nd
element is the 2
nd
harmonic, etc. The accuracy of harmonics may be
limited by the FREQUENCY SPAN setting.
See para. 4.3.1.1 and 5.4.1.
:MAG
returns each magnitude as a percent of the fundamental.
:
ABS
returns absolute magnitude
:MEASure:SPECTrum:PHASe?
(option: Harmonic Analysis and Synthesis)
Query: phase angles in degrees for the most recent harmonics data
Returns a data set of 51, NR2 type numbers, comma delimited. The
1
st
element is the angle of the fundamental, for reference. The 2
nd
element is the angle of the 2
nd
harmonic, etc. The previous
:MEASure:SPECTrum:parameter
command defines which phase
angles are sent. If parameter was VOLT1 then the phase angles will
be for VOLT1.
:MEASure:SPECTrum:THD?
(option: Harmonic Analysis and Synthesis)
Query: Returns Total Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter
command, as above.
:MEASure:SPECTrum:OHD?
(option: Harmonic Analysis and Synthesis)
Query: Returns Odd Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter
command, as above.
:MEASure:SPECTrum:EHD?
(option: Harmonic Analysis and Synthesis)
Query: Returns Even Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter
command, as above.
Summary of Contents for UPC-1
Page 2: ......
Page 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Page 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Page 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Page 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...