background image

070509-16 

VISTA and CLASSIC-C 

7

5055.3

Canada Only

RESIDENTIAL INSTALLATION

Warning:  Under  no  circumstances  is  this  heater  to  be 

installed in a makeshift or "temporary" manner. It may be 

fired only after the following conditions have been met.

•  DO NOT ATTEMPT TO CONNECT THIS HEATER TO 

ANY AIR DISTRIBUTION DUCT.

•  The services of a competent or certified installer, certi

-

fied by the Wood Energy Technical Training program 

(WETT)  -  in  Canada,  Hearth  Education    Foundation 

(HEARTH) - in U.S.A., are strongly recommended.

•  Outside combustion air may be required in your area, 

consult local building codes.

CLEARANCES

1.  This heater may be installed using a single-wall connector 

(smoke pipe) or a listed double-wall connector.

Pacific Vista and Vista Classic:

  Clearances to combustible 

surfaces and materials are shown in Figure #1a, page 4.

Clearances may be reduced with various heat insulating materi-

als. Consult local fire codes and authorities for approval.

CHIMNEY

Connect  to  a  listed  Factory-Built  Chimney  or    a  chimney 

suitable  for  use  with  solid    fuel  that  is  lined  and  in  good 

condition and meets building code.  Chimney flue exit is to be 3' 

(1 m.) above roof and 2' (.6 m.) above the highest projection 

within  10'  (3  m.).    The  installation  must  meet  all  local 

codes.  Do not connect this unit to a chimney flue serving another 

appliance. Minimum chimney height is 15' (4.6 m.) measured from 

base of appliance.

DOUBLE-WALL CONNECTOR

*  Use  a  listed  double-wall  connector  for  use  with  solid 

fuel.

*  Install all components to the chimney connector manu-

facturer's installation requirements.

SINGLE-WALL CONNECTOR (Smoke Pipe)

Smoke pipe must be:

*  secured  at  every  joint  and  collar  with  3  sheet  metal 

screws

*  installed with the crimped or male ends pointing down.  This 

will carry any liquid creosote or condensation back into 

the stove

*  The chimney connector should not pass through attic or roof 

space, closet or similar concealed space, or floor, ceiling, 

wall,  or  partition  of  combustible  material.    Floor 

protection is required under horizontal chimney connector 

and 2" beyond each side.

PROCEDURE

1.  If  a  listed  chimney  and  double-wall  connector  is  to  be 

connected to the stove, see MOBILE HOME INSTALLA

-

TION section.  (Outside combustion air may not be required, 

consult local building codes.)

2.  If it is desirable to use single wall connector in conjunc-

tion with insulated chimney, see step 4.

3.  If  a  roof  or  ceiling  support  is  used  in  the  installation, 

you will find the chimney manufacturer's complete instruc

-

tions packed with the roof support.

4.  To  start  installing  single  wall  connector  (smoke  pipe), 

slip crimped edge of the pipe inside the stove collar.  Use 

holes provided in collar to secure pipe with two screws.

5.  Install  the  remaining  lengths  of  pipe  one  on  top  of  the 

other to the finished height of the chimney connector and secure 

to each other.  When approaching the ceiling, slip the ceiling 

trim plate and joist shield over the chimney so that after 

the chimney is extended through the ceiling, the trim plate can 

be secured to the ceiling.

FLOOR PROTECTOR

The stove may be installed on a combustible floor provided 

non-combustible protection is used.

This protection must extend as follows:

In Canada:

  18" (457 mm) on the firing side and 8" (203 mm) 

to the other sides.  See Figure #3a below.

In USA:

  16" (406 mm) to the front and 8" (203 mm) to the 

fuel loading door opening.  See Figure #3b below.  This pro-

tection is also required under the chimney connector and 2" (51 

mm) beyond each side.

FIG. #3a

Minimum Width - 32"

Minimum Overall Depth - 33 1/4"

U.S.A. Only

Minimum Width - 40"

Minimum Overall Depth - 43 1/4"

FIG. #3b

Non-combustible  Floor Protector

Non-combustible  Floor Protector

Summary of Contents for Pacific VISTA

Page 1: ...IES C SAFETY NOTICE If this stove is not properly installed a house fire may result For your safety follow the installation directions Contact local building or fire officials about restrictions and i...

Page 2: ...AFETY AND MAINTENANCE 3 ASSEMBLY 4 MOBILE HOME INSTALLATION 6 RESIDENTIAL INSTALLATION 7 FLOOR PROTECTOR 7 COMBUSTION AIR 8 WOOD SELECTION 8 OPERATING 8 PROPER DRAFT 9 ASH REMOVAL 9 BAFFLE REMOVAL 9 O...

Page 3: ...nnect the detectors If necessary relocate them to reduce their sensitivity safety notice If this stove is not properly installed a house fire may re sult For your safety follow the installation direct...

Page 4: ...pedestal mounting holes with the studs on stove bottom 2 Secure in place with 1 2 nuts previously removed 3 Carefully place the unit in an upright position LEG KIT 1 With the unit on its back and remo...

Page 5: ...e Chimney Roof flashing Storm collar Hooded vent Attachment to floor for mobile homes Spark arrestor rain cap FIG 2 7 2 1 m Minimum Ceiling Height 58 1473 mm Minimum 48 1219 mm Minimum The chimney may...

Page 6: ...upplier for installation advice PROCEDURE Note See Combustion Air section on page 8 1 Position stove and floor protection with the clearances as stated on the label or as in Figure 1a and 1b page 4 5...

Page 7: ...spointingdown This will carry any liquid creosote or condensation back into the stove Thechimneyconnectorshouldnotpassthroughatticorroof space closet or similar concealed space or floor ceiling wall o...

Page 8: ...der no circumstances should you attempt to barbecue in this heater HOW TO TEST YOUR WOOD Add a large piece of wood to the stove when it has a good large bed of coals It is dry if it is burning on more...

Page 9: ...rough appliance and chimney connector joints indicates inadequate draft ASH REMOVAL When ever ashes get 3 to 4 inches deep in your firebox and whenfirehasburneddownandcooled removeexcessashes Leave an...

Page 10: ...sket leakage Replace gasket Check latch EXCESSIVE CREOSOTE BUILDUP See 1 2 3 above LOW HEAT OUTPUT 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or re...

Page 11: ...excessively open When wood is burned slowly it produces tar and other or ganic vapours which combine with expelled moisture to form creosote The creosote vapours condense in the relatively cool chimn...

Page 12: ...CAST VSNI 9 DOOR HANDLE ASSEMBLY WODC 4147 10 BOOST MANIFOLD 2105 11a FIREBRICK 1 1 2 x 4 1 2 x 1 1 4 248 11b FIREBRICK 3 x 4 1 2 x 1 1 4 247 11c FIREBRICK 4 x 4 1 2 x 1 1 4 246 11d FIREBRICK 9 x 4 1...

Page 13: ...7 11c FIREBRICK 4 x 4 1 2 x 1 1 4 246 11d FIREBRICK 9 x 4 1 2 x 1 1 4 5096 99 FIREBRICK SET BRIC VISTA 12a BRICK RAIL LEFT 2122 12b BRICK RAIL RIGHT 2122 5 13 RAIL EXTENSIONS 2 pc required 2123 14 BAF...

Page 14: ...the heater in the upright position install firebricks as follows First install 4 full size firebricks against the rear wall Next install the side firebricks 2 full size each side Lastly place 4 full...

Page 15: ...JET MODEL HT 3000 SELKIRK SENTINEL MODEL CF INDUSTRIAL CHIMNEY MODEL EXCEL 2100 ENERGY VENT COMMANDER 5000 IN USA SECURITY MODEL ASHT OR S2100 OLIVER MACLEOD MODEL 3103 OR HT 3000 SELKIRK METALBESTOS...

Page 16: ...16 VISTA and CLASSIC C 070509 16 5055 3 Printed in Canada PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan BC V9L 6V8 Phone 888 715 2398 Web site www pacificenergy net...

Reviews: