VZR.235900.000 IG
Cube С-04 Turnstile
Installation Guidelines
19
5.1 Power supply connection
DO NOT
:
USE POWER SUPPLY UNITS WITH AN OUTPUT CURRENT OF LESS THAN
3.0 A.
ENERGIZE THE TURNSTILE USING A POWER SUPPLY CABLE WITH A
CROSS SECTION OF LESS THAN 1.5 MM
2
WITH THE FEEDER CABLE
BEING MORE THAN 10M LONG – A 2.5 MM
2
CROSS-SECTION CABLE IS
RECOMMENDED.
ATTENTION:
INSTALLING THE POWER SUPPLY UNIT AT A DISTANCE
OF OVER 25 M FROM THE TURNSTILE IS NOT RECOMMENDED.
The turnstile is powered by a 12 VDC unit. Max consumption – 3.0 A.
PSU shall be selected based on these parameters.
Also, it should be considered that when increasing the feeder cable length,
the voltage drop increases (operating voltage range is specified in Operational
Manual VZR.235900.000 RE).
Install PSU in a location easy to access for the operator.
Connect PSU cable to the group of co12U_IN and GND_IN on the
motherboard. Connect PSU’s (+) and (-) contacts to (12V_IN) and (GND_IN)
contacts accordingly.
Make sure the cable is secure.
5.2 Control Panel Connection
Connect RC panel to the group of contacts
Pult
on the motherboard.
Labeling of contacts: 12V, CL, CH, GND.