ClimaCon F
Mounting
6.4.1.6 ClimaCon F
310 (24
V
) (item no.
1155531)
Terminal
Assignment
1
IN (L1 24 V AC) operating voltage
2
IN (L2 24 V AC) operating voltage
3
OUT (L1 24 V AC) on/off / PWM
4
OUT (L1 24 V AC) setback output
5
IN (L1 24 V AC) change-over,
not potential-free
6
IN (A) ext. 10 K NTC
7
IN (B) ext. 10 K NTC
8
OUT (signal) 0-10 V (max. 10mA)
9
OUT (NO) potential-free contact
(max 24 V, 90 mA DC/AC)
10
OUT (COM) potential-free contact
(max 24 V, 90 mA DC/AC)
L1
L1
L1
1
2
3
4
5
9
10
6
7
8
L2
CO S1
NO
COM
0-10
L1
L2
SELV
NTC
10 K
ϑ
DI
(ON/
OFF)
AI
(0-10V)
6.4.2 Connection of the room thermostat
NOTICE
Damage to the ClimaCon due to several outer
conductors (phases) in the installation!
!
Use the same outer conductor (phase) for
terminals 1 (operating voltage), 4 (setback input
or setback output) and 5 (change-over).
If this is not possible on site, ensure the
separation of the phases by means of a coupling
relay.
WARNING
Only ClimaCon F
310 (24
V
) (item no. 1155531)
Danger to life due to excessive voltages at the
terminals for potential-free contacts!
!
Only apply extra-low voltages (SELV) to
terminals 9 and 10.
f
Connect the cores to the terminal strip according to the
terminal assignment for your product variant (stripping
length 6 mm).
6.4.3 Fitting of the control unit
NOTICE
Damage to the device due to incorrect operating
voltage!
Mounting plates and operating elements of the
different product variants are not compatible with
each other.
!
Only combine components of the same product
variant with each other.
f
Connect the control unit to the mounting plate by
first placing the control unit on the lower edge of the
mounting plate and then pressing it on with a slight
twisting motion.
Z
The room thermostat is completely mounted when
the release clip is audibly engaged.
Fig. 10: Fitting of the control unit
6.5 App installation (F
210, F
310)
The ClimaCon F app is available for both Android
and iOS.
Note the minimum requirements regarding the
version of the operating system and the
Bluetooth version (see par. 3.5 on page 10).
1
Go to the Appstore for your operating system.
2
Search for the Oventrop App “ClimaCon” and install it.
15
115500984-V07.11.2022