ClimaCon F
Commissioning
Fig. 21: ClimaCon F App - Entering the installer code
f
To call up the extended settings, enter the installer code
2962 and confirm the entry with "OK".
7.2.5 ClimaCon F
210, F
310 - Extended
settings
NOTICE
Malfunctions due to improper configuration!
Improperly configured extended settings can cause
unexpected room temperatures and damage parts
of the system.
!
Extended settings may only be carried out by
specialist tradespeople who are sufficiently
qualified.
7.2.5.1 Unit
Here you can choose between the units °Celsius
and °Fahrenheit.
This setting affects all temperature settings in the
app and at the room thermostat.
7.2.5.2 Operating mode
Here you can switch between the operating
modes.
•
ClimaCon F
210: Heating / Cooling
•
ClimaCon F
310: Heating / Cooling / Heating or
cooling
7.2.5.3 Sensor (F
310 24
V)
The room temperature can be measured via the
internal sensor or optionally via an external
sensor.
Here you select which sensor is to be used.
7.2.5.4 External limitation (F
310 24
V)
If a temperature sensor is connected to measure
the surface temperature, the maximum/minimum
permissible temperatures can be set here.
If these temperatures are exceeded or undercut,
the connected actuator is closed.
This can only be selected if the internal sensor is
used for temperature measurement.
7.2.5.5 Output signal of the actuator
Electrothermal actuators can be wired with an on/
off control or pulse-width modulation.
For surface heating systems, we generally
recommend pulse-width modulation (PWM). This
enables a fast and accurate reaction to
temperature differences between the measured
actual values and the defined setpoint values.
With PWM control, the opening and closing time
of the actuator is calculated from the temperature
difference between the actual value and the
setpoint value.
The higher the difference, the longer the actuator
remains open.
By setting a hysteresis, you define the value by
which the measured temperature may deviate
from the setpoint temperature before the
actuator is opened for heating or cooling.
The optimum value depends on the design of the
system.
7.2.5.6 Output signal 0 - 10
V (ClimaCon F
310 (24
V)
The reaction of the 0-10 V output is influenced by the P
and I components.
P component
Setting of the height of the proportional band of the PI
controller.
I component
Setting of the height of the integral component of the PI
controller.
7.2.5.7 Valve protection
Once a week, the actuator is fully opened and
closed. This ensures that the valve cannot get
stuck during a longer standstill.
The point in time within the week can be set here.
20
115500984-V07.11.2022