ClimaCon F
Commissioning
Fig. 18: ClimaCon F app - Manual time entry
7.2.4 ClimaCon F
210, F
310 - Configuration
f
Tap “Configuration” in the “Settings” menu.
7.2.4.1 Temperature limitation
The maximum adjustable temperature range is
between 12 °C and 28 °C.
The adjustable temperature range can be limited
here.
Example:
If the room temperature is to be at least 18 °C
and at most 25 °C, set the values here accordingly.
With this basic setting, the room temperature can
then only be controlled in the range between
18 °C and 25 °C in the app and on the room
thermostat.
7.2.4.2 Operating mode
The currently set operating mode "Heating" or "Cooling" is
displayed here.
The corresponding setting can be changed in the
“Extended settings” menu (Fig. 20 on page 19).
7.2.4.3 Correction offset
In unfavourable installation conditions, the
temperature measured on the room thermostat
can deviate greatly from the actual room
temperature.
In these cases, you can define a correction offset
to compensate for the deviation.
1
Determine the temperature deviation.
2
Set the correction offset accordingly.
7.2.4.4 Designation
f
Here you can change the name of the currently selected
room thermostat.
7.2.4.5 Symbol
f
Here you can change the symbol for the currently
selected room thermostat.
7.2.4.6 Automatic summer time
f
Select whether the app should automatically switch
between standard time and summer time.
7.2.4.7 Removal of a room thermostat
f
Here you can remove the currently selected room
thermostat.
Z
After the room thermostat has been removed, the app
switches to the start screen (Fig. 12 on page 16).
7.2.4.8 Firmware room thermostat
1
Fig. 19: ClimaCon F app - Firmware update
1
Call-up of the firmware update
7.2.4.9 Extended settings
1
Fig. 20: ClimaCon F app - Call-up of the extended
settings
1
Call-up of the extended settings
19
115500984-V07.11.2022