L-737-3-E
6.5 Pulse Output Wiring
When pulse output is to be connected to a receiving instrument, Pulse Output has terminals P (
+
) and
terminal P (
-
) while Pulse Output has terminal P (
+
) and terminal P (
-
).
If voltage pulse signal is your option, signal transmission length has restrictions on output frequency.
Output frequency
Max. transmission length
※
0kHz
0m
kHz
00m
00Hz
000m
※
Values are based on wire material 0.7 sq in cross section.
To change from voltage pulse output to open drain pulse output, or vice versa, remove the front lid and
select jumper positions as indicated below.
Pulse output jumper
OPEN: Open drain pulse
CLOSE: Voltage pulse
JP3
Pulse output jumper
OPEN: Open drain pulse
CLOSE: Voltage pulse
JP
6.6 Status Output Wiring
Status output appears across terminals S.O. (
+
) and S.O. (
-
).
Status output setup procedure appears in .7.3 Status output.
※
Status output will be invalid if FOUNDATION fieldbus, PROFIBUS PA is selected as communication
interface.
Pulse output setup procedure appears in .7. Analog output.
※
Pulse output will be invalid if FOUNDATION fieldbus, PROFIBUS PA is selected as communication
interface.
Fig..
6.7 Status Input Wiring
Status input appears across terminals S.I. (
+
) and S.I. (
-
).
Status input setup procedure appears in .7. Status input.
※
Status input will be invalid if FOUNDATION fieldbus, PROFIBUS PA is selected as communication
interface.