L-737-3-E
3
※
:
For this function, the setting change is disabled in Write Protect mode (refer to section .).
---3
Drive Output Po.
The threshold value of a drive output can be set up.
See . 00
---
Mode
: Off Active
⇒
With Status output condition "ON", status output is turned off.
: On Active
⇒
With Status output condition "ON", status output is turned on.
See . Off Active
No.
Item
Description
Setup
Default
---
Function
Changes status output assignment. (For detail, see . Status Output Function.)
See .
Error
Status
---- Sensor Fail
: Off
⇒
No assignment to status output, : On
⇒
Sensor Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Sensor Fail, see 0. Error Messages.
See . Off
---- Txr Fail
: Off
⇒
No assignment to status output, : On
⇒
Txr Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Txr Fail, see 0. Error Messages.
See . Off
----3 Cal Fail
: Off
⇒
No assignment to status output, : On
⇒
Calibration Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Calibration Fail, see 0. Error Messages.
See . Off
---- Satura. Alm.
: Off
⇒
No assignment to status output, : On
⇒
Saturated alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Saturation alarm, see 0. Error Messages.
See . Off
---- Param Alm.
: Off
⇒
No assignment to status output, : On
⇒
Parameter alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Parameter alarm, see 0. Error Messages.
See . Off
---- Txr Alm.
: Off
⇒
No assignment to status output, : On
⇒
Txr alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Txr alarm, see 0. Error Messages.
See . Off
----7 Slug Alm.
: Off
⇒
No assignment to status output, : On
⇒
Slug alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Slug alarm, see 0. Error Messages.
See . On
---- Cal in prog.
: Off
⇒
No assignment to status output, : On
⇒
Cal in Progress state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Cal in Progress, see 0. Error Messages.
See . Off
---- Fix Output
: Off
⇒
No assignment to status output, : On
⇒
Fix output state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. ---],
however. For detail of Fix output, see 0. Error Messages.
See . Off
No.
Item
Description
Setup
Default
---
Analog
Selects analog output pattern when an alarm condition occurs (sensor failure, Txr failure, or parameter alarm).
: Downscale
⇒
Produces .mA, : Zero
⇒
Produces mA, 3: Hold
⇒
Produces analog value as it is in
an error, : Upscale
⇒
Produces .mA.
See . Downscale
---
Pulse
Selects pulse output pattern in an error (sensor failure, Txr failure, or parameter alarm).
: Zero
⇒
Stops pulse output, : Hold
⇒
Produces pulse output value as it is in an error,
3: Upscale
⇒
Produces an kHz output.
See . Zero
No.
Item
Description
Setup
Default
--
Function
Changes status input assignment. (See . Status input functions.)
See . No function
--
Mode
Selects status input operating conditions.
: Short Active
⇒
Means that status input is shorted and action begins.
: Open Active
⇒
Means that status input is open and action begins.
See . Short Active
No.
Item
Description
Setup
Default
--
Assigh
Changes H/L alarm assignment. (See . High low alarm functions.)
To validate this setting, it is necessary that H/L alarm be selected at status output assignment.
See . Mass Flow
--
H/L Alm. Type
Selects type of H/L alarm.
: High alarm
⇒
High alarm is active, : Low alarm
⇒
Low alarm is active,
3: H/L alarm
⇒
Both high and low alarms are active.
See . High Alarm
--3
High Alm. Po.
Changes high alarm setting. A value exceeding this setting activates high alarm; when it falls below this
setting by H/L alarm hysteresis [No. --], high alarm condition is reset. A setting smaller than low alarm
[No. --] is not acceptable.
See .3
0.0
--
Low Alm. Po.
Changes low alarm setting. A value falling below this setting activates low alarm; when it exceeds this
setting by H/L alarm hysteresis ]No. --], low alarm condition is reset. A setting smaller than high alarm
[No. --3] is not acceptable.
See .3
0.0
--
H/L Alm. hys
Changes high/low alarm hysteresis setting. Frequent annoying false alarms (repetitive alarm on/off in short
duration) can be alleviated by choosing a larger value. To get an accurate picture of alarm condition, choose
a smaller value.
See .3
0