L-770HP--E
8.6 Analog Output Function
This equipment has the two analog outputs and can output the measurement values by the current output
between mA and 0 mA. When an assignment is changed, please set the higher limit value, the lower
limit value, the low cut value, and the damping value to the optimal values again.
Parameter
Descriptions
Setting range
Standard value
Assign
Analog output assign
Mass Flow / Volume Flow
Density / Temp
Drive Output
Mass Flow
Mode
Output valid / invalid setting
Normal (valid) / Stop (invalid)
Normal
URV
Setting value with the analog output
of 0mA At the setting value, 0mA
is output.
―
―
LRV
Setting value with the analog output
of mA At the setting value, mA is
output.
―
―
Lowcut
Analog output low cut
0 to 0 [%]
0 %
Added Damp
Added damping of analog output
0 to 00 [sec]
0 sec
Error output
Analog output status upon
the occurrence of an error
Downscale
:
.mA
Zero
:
mA
Hold
:
Keep the output.
Upscale
:
.mA
Zero
8.7 Status Input Function
This equipment can assign the status input or the status output function to the STATUS I/O terminal.
Switching between status input and status output can be done by changing the parameter (Status IO
Assign) setting.
Parameter
Descriptions
Setting range
Standard value
Status IO Assign
Assigning of status input / output
function
Status input / Status output
Status input
Input function
Selecting of status input
0% Signal Lock / Auto Zero
Reset Total / No Function
No Function
Input logic
Status input logic
Normal Open / Normal Close
Normal Open
■
Status input setting method
(
)
Set Status IO Assign to
“
Status input
”
.
(
)
Select the function to assign to the status input by using Input function.
・
0% Signal Lock
…
Stop pulse output and analog output.
・
Auto Zero
…
Perform zeroing.
・
Reset Total
…
Reset total counter.
(
)
When the STATUS I/O terminal is turned on and kept on for 0. seconds or longer, function is
activated.
(Example) When Input logic is Normal Open, the function is after the terminal is (Close)
for 0. seconds or longer.