L--740--28--E
2-4-5-3
Drive Output Po.
The threshold value of a drive output can be set up.
See 9.4 100
2-4-5-4
Mode
1: Off Active
⇒
With Status output condition "ON", status output is turned off.
2: On Active
⇒
With Status output condition "ON", status output is turned on.
See 9.4 Off Active
No.
Item
Description
Setup
Default
2-4-5-1
Function
Changes status output assignment. (For detail, see 9.14 Status Output Function.)
See 9.4
Error
Status
2-4-5-2-1 Sensor Fail
1: Off
⇒
No assignment to status output, 2: On
⇒
Sensor Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Sensor Fail, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-2 Txr Fail
1: Off
⇒
No assignment to status output, 2: On
⇒
Txr Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Txr Fail, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-3 Cal Fail
1: Off
⇒
No assignment to status output, 2: On
⇒
Calibration Fail state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Calibration Fail, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-4 Satura. Alm.
1: Off
⇒
No assignment to status output, 2: On
⇒
Saturated alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Saturation alarm, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-5 Param Alm.
1: Off
⇒
No assignment to status output, 2: On
⇒
Parameter alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Parameter alarm, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-6 Txr Alm.
1: Off
⇒
No assignment to status output, 2: On
⇒
Txr alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Txr alarm, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-7 Slug Alm.
1: Off
⇒
No assignment to status output, 2: On
⇒
Slug alarm state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Slug alarm, see 10.1 Error Messages.
See 9.4 On
2-4-5-2-8 Cal in prog.
1: Off
⇒
No assignment to status output, 2: On
⇒
Cal in Progress state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Cal in Progress, see 10.1 Error Messages.
See 9.4 Off
2-4-5-2-9 Fix Output
1: Off
⇒
No assignment to status output, 2: On
⇒
Fix output state is assigned to status output.
No output appears unless Status Out is selected at status output function assignment [No. 2-4-5-1],
however. For detail of Fix output, see 10.1 Error Messages.
See 9.4 Off
No.
Item
Description
Setup
Default
2-4-6-1
Analog
Selects analog output pattern when an alarm condition occurs (sensor failure, Txr failure, or parameter alarm).
1: Downscale
⇒
Produces 2.4mA, 2: Zero
⇒
Produces 4mA, 3: Hold
⇒
Produces analog value as it is in
an error, 4: Upscale
⇒
Produces 21.6mA.
See 9.4 Downscale
2-4-6-2
Pulse
Selects pulse output pattern in an error (sensor failure, Txr failure, or parameter alarm).
1: Zero
⇒
Stops pulse output, 2: Hold
⇒
Produces pulse output value as it is in an error,
3: Upscale
⇒
Produces an 11kHz output.
See 9.4 Zero
No.
Item
Description
Setup
Default
2-5-1
Function
Changes status input assignment. (See 9.15 Status input functions.)
See 9.4 No function
2-5-2
Mode
Selects status input operating conditions.
1: Short Active
⇒
Means that status input is shorted and action begins.
2: Open Active
⇒
Means that status input is open and action begins.
See 9.4 Short Active
No.
Item
Description
Setup
Default
2-6-1
Assign
Changes H/L alarm assignment. (See 9.16 High low alarm functions.)
To validate this setting, it is necessary that H/L alarm be selected at status output assignment.
See 9.4 Mass Flow
2-6-2
H/L Alm. Type
Selects type of H/L alarm.
1: High alarm
⇒
High alarm is active, 2: Low alarm
⇒
Low alarm is active,
3: H/L alarm
⇒
Both high and low alarms are active.
See 9.4 High Alarm
2-6-3
High Alm. Po.
Changes high alarm setting. A value exceeding this setting activates high alarm; when it falls below this
setting by H/L alarm hysteresis [No. 2-6-5], high alarm condition is reset. A setting smaller than low alarm
[No. 2-6-4] is not acceptable.
See 9.3
0.0
2-6-4
Low Alm. Po.
Changes low alarm setting. A value falling below this setting activates low alarm; when it exceeds this
setting by H/L alarm hysteresis ]No. 2-6-5], low alarm condition is reset. A setting smaller than high alarm
[No. 2-6-3] is not acceptable.
See 9.3
0.0
2-6-5
H/L Alm. hys
Changes high/low alarm hysteresis setting. Frequent annoying false alarms (repetitive alarm on/off in short
duration) can be alleviated by choosing a larger value. To get an accurate picture of alarm condition, choose
a smaller value.
See 9.3
0
※
1
:
For this function, the setting change is disabled in Write Protect mode (refer to section 9.2).