background image

Page 25

Page 24

900-0125-

12

-

02 Rev A 

©2017 OutBack Power Technologies.  All Rights Reserved.

B-4.  FLEXnet Relay Set Points

This menu allows the user to adjust the criteria used by the 

Auto

 selection in  

the 

FLEXnet Relay Mode

 menu.  For more information on these criteria, see 

the FLEXnet DC literature.

NOTE

:  The following set points assume N.O. logic as described in 

B-3

.  If N.C. logic is used, all uses of the 

words “close” or “open” are reversed.

Voltage:  High

 — The relay will close upon reaching a specified high voltage level following the appropriate delay.

(Voltage) 

Low

 — After the relay was closed according to the 

High

 voltage set point, it will open again upon reaching a specified low

voltage level (following the appropriate delay; see below).

SOC:  High

 — If voltage conditions are not met, the relay will close when the battery state of charge (SOC) increases to a specified

percentage following the appropriate delay.

(SOC) 

Low

 — After the relay was closed according to the 

High

 SOC set point, it will open again upon reaching a specified low SOC level

following the appropriate delay.

Delay:  High

 — Sets the delay time before the relay closes due to a 

High

 set point.  This applies to either the SOC or voltage settings.

(Delay) 

Low

 — Sets the delay time before the relay opens due to a 

Low

 set point.  This applies to either the SOC or voltage settings.

B-3.  FLEXnet Relay Mode

This menu allows the user to turn on or off an internal relay.  The relay contacts 

are rated for 5 amps at 30 Vdc.  (It provides no voltage of its own.)  The relay   

can be used as a switch to turn other devices on or off.  For more information,   

see the 

FLEXnet Relay Set Points

 menu and the FLEXnet DC literature.

Status

 — The Relay output status is controlled by the <

Off

>,<

Auto

>, and <

On

> soft keys.

<

On

> activates the relay immediately.  Its contacts will remain continuously closed until <

Off

> is selected.

<

Auto

> activates the relay by automatic criteria, according to the option selected in 

Relay Set Points

.

<

Off

> deactivates the relay and prevents any of the 

FLEXnet Relay Set Points

 options from working.  Note that even if the

relay output is set to <

Off

>, it may still be activated by an external option such as AGS.  (See page 26.)

Invert Logic

  – Switches the relay‘s function from N.O. (a normally open state) to N.C. (a normally closed state).  The selections are

N

 (no) and 

Y

 (yes).  Since the default condition is N.O., the 

N

 selection means it remains in this state.  Selecting 

Y

 inverts the logic to

N.C.  The relay will close with an audible click when this occurs.

B-2. Shunt Enable

This menu allows the user to turn on or off any of three shunts   

(current sensors) used by the battery monitor.  These are designated as   

shunts A, B, and C.  For more information on the use of each shunt, see the 

Owner’s Manual

 for the FLEXnet DC.

Y

 (yes) — Instructs the battery monitor to measure the current running through a particular shunt.

N

 (no) — Instructs the battery monitor to ignore the selected shunt.

Battery Monitor Settings

Battery Monitor

Battery Monitor Settings (B)

B-1  

Battery Setup

B-2  

Shunt Enable

B-3  

FLEXnet Relay Mode

B-4  

FLEXnet Relay Set Points

B-5  

Reset to Factory Defaults

B-1. Battery Setup

This menu sets the parameters used by the FLEXnet DC battery monitor  

 

(FN-DC)  to track battery status.  (Many of the figures must be given by the 

battery manufacturer.)     

These settings are “fully charged” parameters.  When they are met, the Home screen SOC percentage 

indicator meter will alternate between light and dark text.  (See the 

MATE3s Overview Guide

.)

Battery Amp-hours

 — Identifies the total size of the battery bank in amp-hours.

Charged Voltage

 — This is the minimum voltage that the batteries must reach during the Bulk or Absorption stages for

the FN-DC to consider the batteries fully charged.

Charged Return Amps

 — Sets the limit to which the current must “trickle down” or decrease before the batteries are

considered charged.

Time

 — Sets the duration the 

Charged Voltage

 and 

Charged Return Amps 

must be maintained before the charging cycle is

considered finished.

Charge Factor 

— Adjusts the anticipated charging efficiency of the batteries.  Because the batteries cannot be 100% efficient,

the battery monitor discounts a certain percentage of the energy used to charge them.  This provides a more realistic estimate of

the amount of charge that has been restored.

See the FLEXnet DC literature for more information on recommended settings.  
See page 44 for the effects of the Profile Wizard on several of these settings.

NOTE

:  The MATE3s has certain additional functions that can be used with the FLEXnet DC.  See 

M-8

 on page 40.

B-5.  Reset to Factory Defaults

This screen allows the user to erase the settings from 

the selected charge controller and start over with the 

values programmed at the factory.  These values are 

listed in the FLEXnet DC literature.   

Entering this screen brings up the query   

Reset FLEXnet DC to Factory Defaults?

Use the soft keys to select 

No

 or 

Yes

.

If <

No

> is selected, the screen returns to the 

Battery Monitor

menu.  No changes will be made to any settings.

If <

Yes

> is selected, the battery monitor’s settings immediately

change to the original factory values.  The screen displays the

message 

FLEXnet DC Restored to Factory Defaults

.   A

<

Continue

> soft key will appear.  Pressing this key returns the

screen to the 

Battery Monitor 

menu.

Summary of Contents for MATE3s

Page 1: ...ks may be registered in the United States and other countries Date and Revision August 2017 Revision B Part Number 900 0125 12 02 Rev B A B C D F B A B MATE3s System Display and Controller Programming...

Page 2: ...such as when to start or stop a generator The MATE3s allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be adde...

Page 3: ...Wizard See the Profile Wizard on page 42 for more information Settings Menus This menu accesses additional menus with settings for the system and for individual devices System Settings S apply to over...

Page 4: ...eyesight vary with each installation The contrast color brightness and backlighting of the LCD can be adjusted to provide the best visibility for a given location Contrast Range is from 1 to 100 from...

Page 5: ...access has been limited by A Challenge Installer Password C Optional Any combination of characters up to 15 characters maximum This name is displayed on the Home screen Set User Access Level A This m...

Page 6: ...nly A and B Turns off the charger for an individual inverter and prevents it from responding to global charger commands Input Support FX class only C Enables the Input Support function if present Not...

Page 7: ...vation The AUX deactivates three minutes after the Enable condition clears and Auxiliary Relay Radian inverters have an additional Auxiliary Relay This is a switched contact with no 12 Vdc output It h...

Page 8: ...L1 inverter for single phase parallel or split phase multiple inverter systems OB Slave L2 A secondary L2 inverter for split phase multiple inverter systems L2 Phase Master The subphase master inverte...

Page 9: ...rtain items such as Voltage Limit which are adjustable in other modes Upload Grid Protection These menus can implement any of several GIP files which can be downloaded from the OutBack website The GIP...

Page 10: ...vated when the GridZero or Grid Tied input modes are selected See page 11 All items described on this page are enabled according to regulatory specifications Grid Support Functions indicates whether t...

Page 11: ...al features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option un...

Page 12: ...g Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Threshold The low voltage setting that activates the output following the Hysteresis Time ON Time The le...

Page 13: ...er to turn on or off any of three shunts current sensors used by the battery monitor These are designated as shunts A B and C For more information on the use of each shunt see the Owner s Manual for t...

Page 14: ...f it had previously been manually disabled CAUTION Equipment Damage This function can damage the generator or the batteries if either are not properly maintained Be sure to follow all maintenance requ...

Page 15: ...of Load Start the inverter will charge the batteries However it is not programmed to perform a complete charge cycle If the generator reaches its Stop point the charge might not be completed State of...

Page 16: ...ing the exercise period This is mostly applicable to DC generators IMPORTANT Regularly running a generator keeps engine components lubricated expels excess moisture charges the starting battery and he...

Page 17: ...two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons Fo...

Page 18: ...X class inverters use Device Type 2 while FLEXmax charge controllers are Type 3 The FLEXnet DC Battery Monitor is Device Type 4 Device Types not depicted here include FXR class inverters Type 5 and Ra...

Page 19: ...stem to reconnect to the utility grid Grid Connect Delay 0 to 240 minutes The delay period after reaching Grid Connect before the system reconnects to the utility grid Grid Disconnect xx x VDC inverte...

Page 20: ...iod is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting EXAMPL...

Page 21: ...for more information on this function If the battery voltage exceeds the target the 12V AUX output will open the ROCB This removes the AC source from the grid tied inverter shutting it down This will...

Page 22: ...ce programming and saving is complete press Exit to return to the Main Menu W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied t...

Page 23: ...battery Capacity in B above See I 6 on page 12 for more information on battery charging Wizard Date Time A Hour Minute Day Month Year Weekday NOTE See S 6 on page 6 for more information on clock setti...

Page 24: ...y pressing Save will automatically default to Option 2 below 1 Select a name on the list with the control wheel Press the Save soft key N to save the new settings over the selected profile Saving to S...

Page 25: ...1 0 01 99 4 12 17 81 2 17 9 0 11 72 2 06 98 4 11 17 83 1 67 9 0 12 54 1 55 98 NOTE This header line is included in the download Device Data Logs D Users can create Device Data Logs for the FLEXmax FM...

Page 26: ...Log is downloaded to an SD card an elg file is created This file can be opened in Notepad or MS Word as a text file Event logs can be used to identify repeated symptoms and other patterns A partial E...

Page 27: ...these steps to help determine the nature of the fault This may also help resolve the problem See the MATE3s Overview Guide for more information on the EVENTS indicator To investigate event messages 1...

Page 28: ...g the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between...

Reviews: