8
PB
. SUGGESTED BATTERY CHARGER SET POINTS
The battery manufacturer should provide you with specific instructions on the following maintenance
and voltage set point limits for the specific batteries. The following information can be used when the
manufacturer’s information is not available.
SEALED LEAD ACID – AGM / GEL
V
V
8V
ABSORB voltage set point
14.4V
28.8V
57.6V
FLOAT voltage set point
13.4V
26.8V
53.6V
NON-SEALED LEAD ACID
V
V
8V
ABSORB voltage set point
14.8V
29.6V
59.2V
FLOAT voltage set point
13.8V
27.6V
55.2V
NOTE:
Higher settings can be used with non-sealed batteries, but water consumption will be greater
and excessive temperatures when recharging may occur.
Battery Voltage and State of Charge
A battery’s voltage can be used as a guideline to estimate the amount of power stored in the battery
that is available for use. When referencing the battery voltage on the display, be sure the battery is not
under significant recharging or heavy loads. Otherwise, the DC voltage is not reflective of the battery
state of cycle. Often the best time to check the battery voltage is in the morning (pre-charging) or at
night (post-charging), with the battery disconnected from charging sources and loads and a rest for at
least three hours.
Operation of a battery below 50% state of cycle will adversely affect the long term health of the
battery system and will result in premature failure. Keeping the battery above the 50% level and
recharging it completely once a month will ensure proper operation and good performance.
STATE OF CHARGE
Nominal Battery
Charged Good (~75%) Average (~50%) Low (~25%) Discharged
Voltage
12V
over 12.6V
12.3V
12.0V
11.7V
under 11.4V
24V
over 25.2V
24.6V
24.0V
23.4V
under 22.8V
48V
over 50.4V
49.2V
48.0V
46.8V
under 45.6V
60V
over 63.0V
61.5V
60.0V
58.5V
under 57.0V
Summary of Contents for FLEXMAX 80
Page 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Page 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Page 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Page 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Page 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...