0
PB
Auto
(default) leaves backlight and soft keys on for
up to nine minutes whenever any soft key is pressed
(pressing any soft key when the LCD is
not
lighted
does not change any settings). Minutes are adjustable
using the
< ->
and
< + >
soft keys.
On
or
Off
states are also available.
Press the
<EXIT>
soft key twice to return to the
MAIN
Menu screen
Press the
< >
soft key to move the “
g
“ to the
EQ
option. When the
g
is to the left of
EQ
, press the
<GO>
soft key.
Charger Aux
g
Light
EQ Misc Optimize
Logging Stats
EXIT
f
g
GO
BACKLIGHT CONTROL
Auto Time 2 Minutes
Auto
EXIT - + MODE
On
Off
Auto
0. Backlight
. EQ—Battery Equalize
The intent of an equalization charge is to bring all battery cells to an equal voltage. Sealed batteries
should not be equalized unless specifically instructed by the manufacturer. Shut off or minimize all
loads on the battery. When equalizing, be sure the EQ voltage will not damage any still energized DC
load. If possible, ensure the EQ cycle starts and stops the same day it is initiated or unnecessary battery
gassing will occur.
• Occasional equalization extends the life of flooded electrolyte batteries.
• Proceed with caution! A vent fan is recommended in enclosed spaces.
• The FLEXmax 80 allows the user to set voltages and times of equalization process.
• Both manual and auto modes are available.
• EQ voltage is
not
battery temperature compensated.
•
Always check the electrolyte level in the batteries before and after equalizing.
Summary of Contents for FLEXMAX 80
Page 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Page 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Page 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Page 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Page 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...