PB
FLEXmax 80 Internal Fan
• The internal fan will only run when the internal temperature has reached approximately 112°F. The
fan will continue running until the internal temperature is less than 104°F.
FLEXmax 80 is beeping
• When the FLEXmax 80 is in
Extended Play
mode, the array is very hot, and the MPP is close to the
battery voltage, or the nominal PV voltage is higher than the nominal battery voltage, beeping can
occur. To disable the
Extended Play
feature, go to the MAIN Menu and press and hold the #1 soft key
until the FLEXmax 80’s software version appears on the screen. Continue pressing the #1 soft key and
press the #3 soft key at the same time until
X Off
displays on the screen. To reactivate
Extended Play
,
repeat these steps and hold the #3 soft key until
X On
displays.
Extended Play
is meant to optimize
the performance of a hot array, but isn’t critical to efficient FLEXmax 80 operations.
To enable/open the FLEXmax SELECT VERSION screens:
• Turn off the DC and array breakers
• Press and hold the first and third soft keys
• Turn on the battery breaker
• Follow the SELECT VERSION screen instructions from the beginning of the manual
• Rebooting the FLEXmax 80
like this
will return all the values and set points to the factory defaults.
DC Breakers /
Battery Breaker
Press and hold the first
and third soft keys
Figure 9
Summary of Contents for FLEXMAX 80
Page 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Page 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Page 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Page 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Page 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...