background image

19

8

7

6

5

D

C

B

A

B

C

D

E

F

1

2

3

4

5

6

7

8

F

E

A

Date

Pages

Author

Designer

Scale

Document type

Document description

Item

Document code and revision

1/1

Modifier

Page size

1:1

A4

XL740-A-01

Printing color: RAL 9005 Jet Black

Drawing

OUFLEXMINI PRINTED COVER

09.06.2015

MM

--

--

XL740

9 10

11 12

13 14

15 16

17 18

19 20

C NO

C NO

C NO

C NO

C NO

C NO

1 2

3 4 5

6 7 8

24V ~/+ 

B2 A2

B1 A1

21

22 32 42

25

62 72 82 29 03 13 23 33 43 53 63

37

83 93 04

41

24 34 44

45

64 74 84 49 05 15 25 53 45 55 65

57

85 95 06

Y1

PWM

Y3

2Y

M5

4Y

M4

M3

M2

M1

M14

51

M

M12

31

M

M10

M11

M9

M8

M7

M6

Print1)

Print2)

Print3)

6

6

6

6

6

1

2

2

5

Detachable strip connectors

  

(analog outputs and PWM). 

Connector labels:

       

       

 

31       0…10 V output (Y4) 

32                   

GND

    

 

33        0…10 V output (Y3) 

34                   

GND

35        0…10 V output (Y2) 

36                   

GND

37    0…10 

output 

(Y1) 

38                   

GND

39    PWM 

40                   

GND

Detachable strip connectors

  

(passive sensors and  

digital inputs). 
21 

    M1        

22 

      

GND

  

23    M2        

24 

      

GND

  

25    M3        

26 

      

GND

  

27    M4        

28 

      

GND

  

29    M5        

30 

      

GND

  

41 

    M6      

42 

      

GND

  

43    M7        

44 

      

GND

  

45    M8        

46 

      

GND

  

47    M9        

48 

      

GND

  

49    M10 

      

50 

      

GND

 

3

Detachable strip connectors

  

(passive sensors, active sensors and  

digital inputs). 
51 

    M11 

      

52 

      

GND

  

53    M12 

 

54 

      

GND

  

55    M13 

 

56 

      

GND

  

57    M14 

    

58 

      

GND

  

59    M15 

  

60 

      

GND

  

3

3

3

3

3

5

5

5

5

5

3

3

3

3

3

4

4

4

4

4

6

Detachable strip connectors

  

(relays with normally open  

contact max 230 Vac, 5 A). 

Connector labels:

      

9      Relay 1 C  

10     Relay 1 NO 
11     Relay  2 C  

12     Relay  2 NO 
13     Relay 3 C  

14     Relay 3 NO 
15     Relay 4 C  

16     Relay 4 NO
17     Relay 5 C  

18     Relay 5 NO 
19     Relay 6 C  

20    Relay 6 NO

RS-232 connection  
(External display)

RS-232 connection (Oulink, 
SMS-modem)

USB-connector

2

Detachable strip connectors 

(RS-485-bus connectors)   

Connector labels

:             

3                   

 

GND

   

    RS-485-bus 

connection B2 

    RS-485-bus 

connection A2   

6                  

 

GND

            

7     RS-485-bus 

connection B1 

    RS-485-bus 

connection A1 

 

1

Detachable strip connectors  

(operation 

voltage). 

     

Connector 

labels:             

1          24 Vac operation voltage output

2      

 

 

 

GND             

Micro-SD memory card slot

4

Ouflex M structure

Summary of Contents for Ouflex M

Page 1: ...pplication to the controller by using SD card M OUFLEX USER MANUAL Ouflex M is a DIN rail attachable monitoring controlling and regulating device Ouflex M can be as a master device and slave device in...

Page 2: ...he beeper stops The beeper can be turned off with active alarms present by pressing the ESC button When you do so the window with details of the most recent alarm on the screen will close To view acti...

Page 3: ...isplay settings 9 1 5 Type information 9 1 6 Lock code 9 1 7 Restore settings and updates 10 2 Alarms 11 3 Point info 13 3 1 Wiring info 13 3 2 Bus points 13 3 3 Time programs 13 4 Settings 15 5 Measu...

Page 4: ...vings and leap years into account automatically The clock has a backup for power outages lasting at least three days 1 Set hours and press to accept 2 Set minutes and press to accept 3 To exit without...

Page 5: ...S e g TC01 IN PUTS Signal strength Signal strength is expressed with the following descriptions Excellent Good Moderate Low Very low and Initialization failed If signal strength indicates No network t...

Page 6: ...rt RJ 45 located in the side of the controller The maximum length of the RJ45 ethernet cable between Ouflex M and Oulink is 10m and all 4 pairs must be con nected SMS PIN Approve Press and hold OK Can...

Page 7: ...have the same bus address All devices in the bus should be set to the same setting value of the baud rate data bits stopbitteihin and parity System settings Network settings Modbus TCP IP If the Ouma...

Page 8: ...billing information to the Ouman system and activates the service based on the serial number of the Oulink After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be...

Page 9: ...Network settings Display settings Type info Lock code Not in use Lock code In use Not in use Give lock code 0 0 0 0 Approve Press and hold OK Cancel Press and hold ESC When lock code is taken in use...

Page 10: ...microSD memory card from Ouflex M 2 Wait until error message Memory card error is shown in the display 3 Insert new microSD memory card which includes new software to Ouflex M 4 Ouflex M asks if you...

Page 11: ...t alarm history Routing schedule Alarm receivers Alarm sound On 2 Active alarms 07 12 2016 12 24 52 Risk 08 01 2017 01 12 40 Sen 2 Risk of freeze PR 1 GROUP 1 Pump has stopped 0 Received 06 11 2017 02...

Page 12: ...Adding a new switch time 1 Press at the Add new row 2 Press Set the switch time for alarm routing set hours and mi nutes separately and press 3 Press OK and then turn the control knob to set the alarm...

Page 13: ...rcuit board temperature The outputs have a Sounder selection which allows you to set the alarm sound off if you want In the bus points menu you can see those devices which are con nected to the bus By...

Page 14: ...ng mode Weekly schedule 0 3 6 9 12 15 18 21 24 MO TU WE Exception schedule Point info Time programs Exception schedule You can easily make changes that differ from normal routine use by using the exce...

Page 15: ...s You can hide show these settings by pressing OK for a few se conds When visible these settings are shown slightly indented Settings that require maintenance code There is a symbol in front of these...

Page 16: ...prove Press and hold OK Cancel Press and hold ESC A t Name of room 1 6 Naming Huoneiden valinta Huoneen 1 nimi Huone 1 Huoneen 2 nimi Huone 2 r m Automatic control is the mode that is normally used If...

Page 17: ...write the key word using capital or small letters Write only one key word per message Store the key words into your phone s memory If a GSM modem is connected to the Ouflex M you can communicate with...

Page 18: ...dem Do not pull the slot out of the modem without pres sing the SIM card release button first Insert SIM card into the slot and make sure it settles properly Push the slot back to its place Set the SI...

Page 19: ...M3 26 GND 27 M4 28 GND 29 M5 30 GND 41 M6 42 GND 43 M7 44 GND 45 M8 46 GND 47 M9 48 GND 49 M10 50 GND 3 Detachable strip connectors passive sensors active sensors and digital inputs 51 M11 52 GND 53 M...

Page 20: ...M11 M15 5 pcs active sensors 0 10 V M11 M15 from HW ver 1 0 Analog outputs Y1 Y4 4 pcs Output voltage range 0 10 V Output current max 10 mA output PWM output 1 piece that works in parallel with the Y1...