 Special days

AHU control ->Time programs -> Special days

You can enter special day programs as exceptions to normal week-

ly schedule.  You can designate a maximum of 7 special day po-

grams (SD). A special day program is typically created for each 

holiday. When the special day program will be applied it is set in 

the exception schedule.
Adding a new switch time: 

1.  Navigate to ”Special days” and press   . Select an unused special 

day and press   .

2.  Place the cursor on ”Add new” and press   . Set the time for the 

program (hours and minutes are set separately). Select the mode 
to be switched to at the time specified. Accept the program by 
pressing    when the cursor is on   .

3.  Navigate to the ”Add new” row. Set the time for the mode to deac-

tivate and the device to return to standard control mode.  Accept 
the program by pressing  .  You can set several different AHU 
control modes within one special day.

Editing view

Graph

Special days

0 3 6 9 12 15 18 21 24

SD1 >  

       >

SD2> 
SD3>

1

Time Mode

00:00 Add new

0    6    12   18   24

08:00 On

0    6    12   18   24

2

OK

SD1

SD1

Time Mode

 Settings

 Supply water min limit     12.0 °C >

     Min lmt incr. outd. temp. 3.0 °C>

 Supply water max limit     42.0 °C>
 

 I-control ’s max effect 2.0 °C>

 Settings

Room temperature    21.0 °C>

Temperature drop        1.5 °C>

Big temp. drop               5.0 °C>
Supply wat. min limit  12.0 °C>

In Ouflex M, settings can be classified into the following categories: 
•  Main settings

•  Hidden settings 

You can hide/show these settings by pressing OK for a few se-
conds. When visible, these settings are shown slightly indented.

•  Settings that require maintenance code 

There is a   symbol in front of these settings. If you try to change 

one of these settings, your Ouflex device asks you to enter the 
maintenance code.  

Changing a setting: 

Choose the desired setting by using the   or  knob. Press 

 

 to go to 

the view where editing is possible. Change the setting by using the   
or  knob.
Press 

 

 to accept the change. 

Press Esc to exit the editing view.

You can see the setting range (minimum and maximum value), if there 

is one, in the editing view.

Locking the settings: 

Lock the settings to prevent unauthorized persons from changing them. 

The device will then ask for lock code before it let’s you change the set-

tings. You can lock the settings in Ouflex device system settings. 

 Huonelämpötila

21.0°C

  Room temperature

21.0°C

4 Settings

 

If a GSM modem is connected to Ouflex M device and the setting values have been brought into SMS interface, you can edit 
settings by text message. Send a message “ Key words”. The reply message shows you which key words are in use in the 
application. The example below describes the communication principle. 

Send a message: H1 Settings.

 

The controller sends the main settings to your mobile phone. Editing the setting 
values: write the new setting in place of the old setting and send a message
back to the controller. The controller sends the setting as a return message.

H1 SETTINGS

H2 SETTINGS

H1 Settings:
Room temperature  = 21.5°C/
Temp.drop = 3.0°C/

min: 0.0  max: 95.0

Summary of Contents for Ouflex M

Page 1: ...pplication to the controller by using SD card M OUFLEX USER MANUAL Ouflex M is a DIN rail attachable monitoring controlling and regulating device Ouflex M can be as a master device and slave device in...

Page 2: ...he beeper stops The beeper can be turned off with active alarms present by pressing the ESC button When you do so the window with details of the most recent alarm on the screen will close To view acti...

Page 3: ...isplay settings 9 1 5 Type information 9 1 6 Lock code 9 1 7 Restore settings and updates 10 2 Alarms 11 3 Point info 13 3 1 Wiring info 13 3 2 Bus points 13 3 3 Time programs 13 4 Settings 15 5 Measu...

Page 4: ...vings and leap years into account automatically The clock has a backup for power outages lasting at least three days 1 Set hours and press to accept 2 Set minutes and press to accept 3 To exit without...

Page 5: ...S e g TC01 IN PUTS Signal strength Signal strength is expressed with the following descriptions Excellent Good Moderate Low Very low and Initialization failed If signal strength indicates No network t...

Page 6: ...rt RJ 45 located in the side of the controller The maximum length of the RJ45 ethernet cable between Ouflex M and Oulink is 10m and all 4 pairs must be con nected SMS PIN Approve Press and hold OK Can...

Page 7: ...have the same bus address All devices in the bus should be set to the same setting value of the baud rate data bits stopbitteihin and parity System settings Network settings Modbus TCP IP If the Ouma...

Page 8: ...billing information to the Ouman system and activates the service based on the serial number of the Oulink After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be...

Page 9: ...Network settings Display settings Type info Lock code Not in use Lock code In use Not in use Give lock code 0 0 0 0 Approve Press and hold OK Cancel Press and hold ESC When lock code is taken in use...

Page 10: ...microSD memory card from Ouflex M 2 Wait until error message Memory card error is shown in the display 3 Insert new microSD memory card which includes new software to Ouflex M 4 Ouflex M asks if you...

Page 11: ...t alarm history Routing schedule Alarm receivers Alarm sound On 2 Active alarms 07 12 2016 12 24 52 Risk 08 01 2017 01 12 40 Sen 2 Risk of freeze PR 1 GROUP 1 Pump has stopped 0 Received 06 11 2017 02...

Page 12: ...Adding a new switch time 1 Press at the Add new row 2 Press Set the switch time for alarm routing set hours and mi nutes separately and press 3 Press OK and then turn the control knob to set the alarm...

Page 13: ...rcuit board temperature The outputs have a Sounder selection which allows you to set the alarm sound off if you want In the bus points menu you can see those devices which are con nected to the bus By...

Page 14: ...ng mode Weekly schedule 0 3 6 9 12 15 18 21 24 MO TU WE Exception schedule Point info Time programs Exception schedule You can easily make changes that differ from normal routine use by using the exce...

Page 15: ...s You can hide show these settings by pressing OK for a few se conds When visible these settings are shown slightly indented Settings that require maintenance code There is a symbol in front of these...

Page 16: ...prove Press and hold OK Cancel Press and hold ESC A t Name of room 1 6 Naming Huoneiden valinta Huoneen 1 nimi Huone 1 Huoneen 2 nimi Huone 2 r m Automatic control is the mode that is normally used If...

Page 17: ...write the key word using capital or small letters Write only one key word per message Store the key words into your phone s memory If a GSM modem is connected to the Ouflex M you can communicate with...

Page 18: ...dem Do not pull the slot out of the modem without pres sing the SIM card release button first Insert SIM card into the slot and make sure it settles properly Push the slot back to its place Set the SI...

Page 19: ...M3 26 GND 27 M4 28 GND 29 M5 30 GND 41 M6 42 GND 43 M7 44 GND 45 M8 46 GND 47 M9 48 GND 49 M10 50 GND 3 Detachable strip connectors passive sensors active sensors and digital inputs 51 M11 52 GND 53 M...

Page 20: ...M11 M15 5 pcs active sensors 0 10 V M11 M15 from HW ver 1 0 Analog outputs Y1 Y4 4 pcs Output voltage range 0 10 V Output current max 10 mA output PWM output 1 piece that works in parallel with the Y1...

Reviews: