Chapter 1: General information
CURRENT PROTECTION RELAY - IPR-D
Manual P/N: IPR-D GBM 01/09/2006
1.2
The 5 selectable time-current curve shapes are the following:
- moderately
inverse
- normally
inverse
- very
inverse
- extremely
inverse
- definite
time
The 3 programmed curve types are the following:
- ANSI
- IAC
- IEC / BS142
All curve shapes have a time multiplier (M) allowing modifying the trip time.
For the 3 possible curve types and their shapes see:
Æ
Appendix A
REMARK
:
when selecting the curve for the circuit breaker trip, make sure the max. input current to IPR-D
does not exceed 100 A for more than 1 second
⇒
the wrong combination of time and current could
damage the unit and consequently provoke the loss of protection.
Summary of Contents for IPR-D
Page 2: ......
Page 4: ......
Page 24: ......
Page 34: ......
Page 38: ......
Page 40: ......
Page 42: ......
Page 44: ......
Page 49: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 5...
Page 50: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 6...
Page 51: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 7...
Page 52: ......