Chapter 1: General information
CURRENT PROTECTION RELAY - IPR-D
Manual P/N: IPR-D GBM 01/09/2006
1.1
1. General
information
1.1 DESCRIPTION
Thanks to the measuring of ground currents by means of current transformer (CT), IPR-D current protection relay
can perform protection functions according to ANSI, IAC or IEC standards. Thanks also to the indications at the
digital inputs the device can inform for example about the status of circuit breaker or disconnector to which it is
coupled, operate on the outputs and disable some functions.
1.2 APPLICATIONS
•
Primary or secondary protection for generation and distribution systems.
•
Protection of transformers, overhead lines, cables, motors and generators.
1.3 PROTECTION AND FUNCTIONALITY
Description
ANSI
•
CT primary ratio selectable in 5 A steps (10 A
÷
5000 A).
•
Inverse-time
ground overcurrent ..........................................................................................................
51N / 51G
with curve selection according to ANSI, IAC or IEC/BS142:
- moderately
inverse
- normally
inverse
- very
inverse
- extremely
inverse
- definite
time
•
Instantaneous
ground overcurrent........................................................................................................
50N
/
50G
•
Overload alarm level
•
Integral relay test with or without the output contacts intervention
•
1 trip relay
•
3 auxiliary relays that can be associated with the various functions (2 programmable relays and 1 relay
controlling any loss of auxiliary voltage -SERVICE-).
Information
The following information concerns the use of the Actual values and the Setpoints.
OVERCURRENT PROTECTION
IPR-D continuously checks the ground current in the line by means of its CT and activates an alarm and/or the
circuit breaker trip when a value exceeds the set level (called
Pickup
level):
1. possibility of separately setting of the timed and instantaneous overcurrent;
2. no intrinsic delay of the device is added to the instantaneous intervention;
3. ground overcurrent alarm and trip delay according to time-current curve set and to the entity of current.
Summary of Contents for IPR-D
Page 2: ......
Page 4: ......
Page 24: ......
Page 34: ......
Page 38: ......
Page 40: ......
Page 42: ......
Page 44: ......
Page 49: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 5...
Page 50: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 6...
Page 51: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 7...
Page 52: ......