Servicing Fan Modules
The server continues to operate at full capacity if one or two fan modules is not operational.
You can perform a hot-service on a fan module only when four or five fan modules are
operational.
These topics describe service procedures for the fan modules in the server.
■
“Fan Module Configuration” on page 157
■
■
“Determine Which Fan Module Is Faulty” on page 158
■
“Remove a Fan Module” on page 159
■
“Install a Fan Module” on page 161
■
“Verify a Fan Module” on page 162
Fan Module Configuration
Servicing Fan Modules
157