Table 5-11 (Cont.) Threshold Values for Oracle Exadata Database Machine X4-2
Quarter Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
B
Module 1, phase
1
0
0.1
0.2
B
Module 1, phase
2
0
5
7
B
Module 1, phase
3
0
9
12
(page 5-26) lists the threshold values for Oracle Exadata Database
Machine X4-2 Quarter Rack using a three-phase, high-voltage PDU.
Table 5-12 Threshold Values for Oracle Exadata Database Machine X4-2
Quarter Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
9
11
A and B
Module 1, phase
2
0
3
4
A and B
Module 1, phase
3
0
3
4
5.3.1.3 PDU Thresholds for Oracle Exadata Database Machine X3-2
This section contains the PDU thresholds for Oracle Exadata Database Machine X3-2.
Note:
The values listed here are reliable for use on systems in the configuration
received upon deployment and delivery from the Oracle Factory. Any changes
to this configuration should be modeled in Oracle Exadata Configuration
Assistant (OECA), and the PDU thresholds listed in OECA should then be
used. OECA is available on Oracle Technology Network.
5.3.1.3.1 PDU Thresholds for Oracle Exadata Database Machine X3-2 Full Rack
The following tables list the threshold values for Oracle Exadata Database Machine
X3-2 Full Rack:
•
(page 5-27) Threshold Values for Oracle Exadata Database Machine
X3-2 Full Rack with Single-phase, Low-voltage PDU
•
(page 5-27) Threshold Values for Oracle Exadata Database Machine
X3-2 Full Rack with Three-phase, Low-voltage PDU
Chapter 5
Configuring the Power Distribution Units
5-26