(page 5-55) Threshold Values for Oracle Exadata Storage Expansion
Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, High-voltage PDU
•
(page 5-55) Threshold Values for Oracle Exadata Storage Expansion
Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Three-phase, High-voltage PDU
(page 5-54) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a single-phase, low-voltage PDU.
Table 5-65 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-
phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
10
13
A
Module 1, phase
2
0
6
8
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
6
8
B
Module 1, phase
3
0
10
13
(page 5-54) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a three-phase, low-voltage PDU.
Table 5-66 Threshold Values for Oracle Exadata Storage Expansion Quarter
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-
phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
12
15
A and B
Module 1, phase
2
0
11
14
A and B
Module 1, phase
3
0
5
7
(page 5-55) lists the threshold values for Oracle Exadata Storage
Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2
Servers using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-54