(page 5-34) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a single-phase, high-voltage PDU.
Table 5-27 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Full Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
16
20
A
Module 1, phase
2
0
20
21
A
Module 1, phase
3
0
16
20
B
Module 1, phase
1
0
16
20
B
Module 1, phase
2
0
20
21
B
Module 1, phase
3
0
16
20
(page 5-34) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, high-voltage PDU.
Table 5-28 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Full Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
18
21
A and B
Module 1, phase
2
0
18
21
A and B
Module 1, phase
3
0
17
21
5.3.1.4.2 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 M2
and X4270 M2 servers) Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine
Half Rack:
•
(page 5-35) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, Low-
voltage PDU
•
(page 5-35) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, Low-
voltage PDU
Chapter 5
Configuring the Power Distribution Units