Table 5-46 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
13
17
A and B
Module 1, phase
2
0
12
15
A and B
Module 1, phase
3
0
5
7
(page 5-44) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, high-voltage PDU.
Table 5-47 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
11
14
A
Module 1, phase
2
0
5
7
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
5
7
B
Module 1, phase
3
0
11
14
(page 5-44) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, high-voltage PDU.
Table 5-48 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
11
14
A and B
Module 1, phase
2
0
2
3
A and B
Module 1, phase
3
0
3
4
Chapter 5
Configuring the Power Distribution Units