(page 5-28) Threshold Values for Oracle Exadata Database Machine
X3-2 Full Rack with Single-phase, High-voltage PDU
•
Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with
Three-phase, High-voltage PDU
(page 5-27) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a single-phase, low-voltage PDU.
Table 5-13 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
20
24
A
Module 1, phase
2
0
14
18
A
Module 1, phase
3
0
19
24
B
Module 1, phase
1
0
19
24
B
Module 1, phase
2
0
14
18
B
Module 1, phase
3
0
20
24
(page 5-27) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a three-phase, low-voltage PDU.
Table 5-14 Threshold Values for Oracle Exadata Database Machine X3-2 Full
Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
30
38
A and B
Module 1, phase
2
0
32
40
A and B
Module 1, phase
3
0
30
38
(page 5-28) lists the threshold values for Oracle Exadata Database
Machine X3-2 Full Rack using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-27