INSTALLING NEW FIRMWARE
SNAP PAC Redundancy Option User’s Guide
54
5.
Scroll down to the bottom of the screen and click Update Firmware.
Progress of the upload appears at the bottom of the window. If an error occurs, notice the
onscreen message.
Using the Controller Method
CAUTION: Do not use this method of installing firmware on a fully connected redundant system. It may be
overwritten by the normal backup qualification process.
1.
Turn off either the arbiter or the other controller.
2.
Under Arbiter Management on the PAC Redundancy Manager, click Install Firmware.
3.
On the Install Firmware window, select Controller.
4.
Under Firmware, browse to the firmware location and select the new firmware file.
5.
Scroll down to the bottom of the screen and click Update Firmware.
Progress of the upload appears at the bottom of the window. If an error occurs, notice the
on-screen message.
Installing Firmware to the Arbiter
NOTE: It is OK to install firmware to the arbiter while the system is running.