CHAPTER 3: CONFIGURING A CONTROL SYSTEM
SNAP PAC Redundancy Option User’s Guide
27
27
6.
Select Controller 1, and click “read the current settings” to see if the controller is already set up
for redundancy. If it is, skip to
NOTE: If the PAC Redundancy Manager cannot find the address, you will receive an error message. If
you receive an error message, check the following:
•
Did you enter the IP address correctly when you created the control engine?
•
Is the controller turned on?
•
Is the controller correctly connected to an Ethernet hub using a straight-through cable? Is the PC
on the same subnet as the controller? See the PC’s user’s guide for networking information.
7.
Enter a secondary IP address and subnet for ENET 2 of Controller 1.
The ENET 2 port is used to connect the controllers to each other. The recommended settings
for ENET 2 for Controller 1 are as follows:
–
Secondary IP Address: 172.22.22.2
–
Subnet Mask: 255.255.255.240
NOTE: Make sure the secondary address for Controller 1 is even, such as 172.22.22.2. And, make sure
the secondary address for Controller 2 is odd, such as 172.22.22.3. In addition, the two IP addresses
must be sequential, such as 172.22.22.2 and 172.22.22.3.
8.
Select Controller 2 and repeat the steps above for the second controller.
The recommended settings for ENET 2 for Controller 2 are as follows:
–
Secondary IP Address: 172.22.22.3
–
Subnet Mask: 255.255.255.240
9.
When all the secondary IP address fields are correct, click Apply Settings.