OptiPure SRO70 Installation Manual Download Page 3

SRO70 Installation Manual 

Installing or Replacing QT Cartridges

NOTE: Before installing or replacing QT Cartridges, make 

sure to remove the plugs in the QT heads.

1. Close feed water valve.

2. Twist and pull down to remove cartridges.

3. Line up the upward-arrow on the new cartridge with the upward 

pointing arrow on the head. Push cartridge up into head until it 

stops.

4. Turn to right until it stops. NOTE: labels might not always face 

forward.

5. Open feed water valve.

v

 Installation Requirements

Operating a system on water supplies outside of the 

parameters listed below may lead to premature membrane 

failure. This product is for commercial use only and must be 

installed and maintained in accordance with manufacturer’s 

guidelines and local regulatory plumbing codes.

Operating parameters
Typical Membrane TDS rejection:  97+% 

Feed Temperature:  40 - 100° F (4 - 38° C)

Feed pressure:  50 - 80 psi (3.4 - 5.9 bar) at 1 gpm

Production (at 77°F, 60 psi):  70 gals/day (2.9 gals./hr) 

Recovery:  up to 33%
IMPORTANT NOTE: The production rate is strictly 

dependent on feed water temperature and pressure.  

For example: Operating pressure of 30 psi will reduce 

production by 50%, or 48˚F feedwater will reduce production 

by 50%.  

Location
The system should be installed indoors, within 25 ft of the  

equipment water is being supplied to, and protected from 

the elements.  Do not let the processor or storage tank 

freeze or be exposed to rain or direct sunlight.

Feed water connection
An adequate flow and pressure of water to the unit is 

essential for successful operation. 

Drain
A drain should be located within 5 ft of the system. Drain 

must allow a minimum flow of 2 gals/min. Compliance 

with most local plumbing codes requires installation of an 

approved air gap in the drain line. The drain connection 

should be accessible for system set-up and service.

Feed-water chemistry
Feed TDS:  Up to 1200 ppm

Feed pH:  6 - 10

Hardness:  12 grains or less

Free chlorine:  <2 mg/l

Iron (Fe):  0.1 mg/l max.

Turbidity:  <0.05 NTU

Manganese:  0.05 mg/l max.

Hydrogen sulfide:  0.0 mg/l
Note: The presence of silica or flocculants such as alum or 

cationic polymers in the feedwater may cause membrane 

fouling and may require special chemical pretreatment or 

periodic membrane cleaning. Please note that membrane 

failure due to fouling is not covered by the warranty.

Storage Tank
The tank must be located within 10 ft of the water processor. 

The floor beneath the storage tank should be smooth, clean 

and free of sharp objects that could puncture the bottom of 

the tank. 

Optimized Water Lines to Equipment
Tubing, piping and associated fittings connecting Optimized 

water lines to equipment should be food grade material that 

meets NSF Std 51 or 61 with a minimum pressure rating of 

75 PSI.  Optimized water may react with most metal piping 

imparting a bad taste. Plastic pipe or reinforced opaque 

beverage tubing are acceptable choices for Optimized water 

distribution.  The larger inside diameter tubing or hose, the 

better to minimize pressure drop.

2

3

4

Summary of Contents for SRO70

Page 1: ...nual Rev 2 2 SRO70_Simple_Install_v2 2 indd 2018 Procam Controls Inc All Rights Reserved Access manuals spec sheets and additional educational materials for foodservice water treatment at our website...

Page 2: ...relative humidity 80 at 88 F 31 C 4 Installation category II 5 Pollution degree II 6 Indoor use only protect from elements Safety Instructions 1 Please read and follow these instructions when connecti...

Page 3: ...to rain or direct sunlight Feed water connection An adequate flow and pressure of water to the unit is essential for successful operation Drain A drain should be located within 5 ft of the system Dra...

Page 4: ...stalling keep line from the Tank to the equipment as short as possible to minimize pressure loss Avoid loops or kinks in tubing Do not cut tubing with wire crimpers or dikes IMPORTANT PROTECT PROCESSO...

Page 5: ...rs or attach directly to studs Be sure to allow 3 clearance below cartridges for removal Step 2 Route the loose end of 1 4 black tubing from processor to a suitable drain and fasten it at the drain So...

Page 6: ...own in this example Connect the other end to the Feed Water Inlet on processor Step 4 Install the tank valve on the top of the tank Connect a piece of 3 8 blue tubing to tank valve Connect the other e...

Page 7: ...ntil all air is purged from system and product water becomes clear Close the feed valve Step 6 The system includes an optional auxiliary connection This connection provides equipment with water that h...

Page 8: ...increase production or determine if higher capacity system is required Install optional Feed Water Pres sure Booster Pump Determine if the demand is unusual or inconsistent or resize system Poor water...

Reviews: