25
2
The POWER (EMERGENCY STOP) and STEAM switches are
on. The POWER light is on and the alarm beeps once.
This is normal operating condition.
3
The POWER (EMERGENCY STOP) and STEAM switches are
on. The POWER & WATER PUMP RUN light are on, and the
alarm beeps once.
This is normal operating condition. The WATER PUMP RUN
light will go off momentarily. (See page 9 “Initial Operation”)
4
Float switch is not detecting water in the water tank due to:
1) Water shortage; OR
2) Malfunction of the float switch in the tank.
1) Add water to the water tank.
2) Disconnect the wire from the float switch. If the signal clears,
replace the float switch.
5
Float switch in the fuel tank is not detecting diesel fuel due to:
1) Fuel shortage AND/OR
2) Malfunction with the float switch in the tank.
1) Add fuel to the fuel tank.
2) Disconnect the wire from the float switch. If the signal clears,
replace the float switch. (Refer to Guide No.4 figure)
6
Water probe sensors (High, Com, Low) cannot detect water in
the steam vessel because:
1) Not enough water is present in the vessel; OR
2) Water probe sensors(High, Com, Low) are malfunctioning
due to scale build up.
1) Wait until the pump refills the vessel. Once the alarm is
deactivated, normal operation can resume.
2) Clean the water probe sensors. (Refer to Guide No.7
figure)