51
Model
Item
Unit
SP5000 Vitality Eco
Max. Power
W
4000
Inrush Current
A/μS
100/200
Max. Fault Current
A
79
Max. Protection
Over-current
A
79
Nominal Voltage
V
230
Nom. Frequency
Hz
50/60
THDV
%
5
Voltage Regulation
%
2
DC injection
mV
±100
Overload Capacity
600 seconds for 100% ≤ load ≤ 110%
30 seconds for 110% < load ≤ 150%
10 seconds for 150% < load ≤ 200%
General
Temp. Range
°C
-20 ~ 55
4
Max. Eff. (PV/AC)
%
96
Max. Eff. (BAT/AC)
%
92
Protection
IP20
Humidity
%
0~95, non condensing
Cooling
Forced Air-cooling
Variable fan speed control
Protection Class
I
Environment Cat.
Pollution Degree III
Overvoltage Cat.
DC input: II, AC input: III
Amplitude
m
<2000
Reconnect Time
6
S
300
Features
LCD
2-line 16 characters text
Interface
USB, RS485 & CANbus for multiple-unit
operations
RS485
2 wires, half-duplex
Date Logging
Yes
Parallel Operation
Yes