42
AC VOLT HIGH
Vac XXX V
Silent
ACV is higher than
upper limit
AC VOLT LOW
Vac XXX V
Silent
ACV is less than lower
limit
AC FREQ HIGH
fac XX.X Hz
Silent
AC frequency is more
than upper limit
AC FREQ LOW
fac XX.X Hz
Silent
AC frequency is less
than lower limit
PV VOLT HIGH
Vpv XXX V
Cont.
PV is higher than upper
limit
BAT VOLT HIGH
Vbat XX.X V
Cont.
Battery voltage is
higher than upper limit
OVER LOAD
Output is off
Cont.
Output is overloaded
more than defined time,
output is cutoff
O/P Short CKT
REMOVE CKT
Cont.
Output is short
No Battery
Check BAT
Conn.
Cont.
Battery is not
connected
PV-E Low
Insul.
Check PV
Wiring
Cont.
Insulation resistance
between PV and Earth
is too low
CX
No Display
C1~C7 errors, reserved
for internal diagnose
EX
No Display
Cont.
E6~E12 errors,
indicating errors for
multiple connection
Warning message
Line 1
Line 2
Buzze
r
Description
1XX
﹪
Load
Pls. Reduce
Load
On 0.5
Off 0.5
The load is more than
103%, inform user to
reduce load
Low Bat. Cap.
Will Shutdown
On 0.5
Off 4.5
Battery capacity is low.
SP5000 Vitality Eco will
shutdown
Fan Fails
Check or
Replace
On 0.5
Off 4.5
External fan does not
work properly
Summary of Contents for SP5000 Vitality Eco
Page 1: ...Installation Operation Manual SP5000 Vitality Eco...
Page 2: ...This page is intended to be blank...
Page 7: ...5...
Page 18: ...16 Keep distance for the airflow to dissipate heat Mounting Procedure 1 2 3...
Page 24: ...22 Battery sensor Accessory F Protection cover Protection cover From BAT breaker...
Page 29: ...27...
Page 31: ...29 Start up Procedure...
Page 57: ......