Connecting AC Mains
1.
Open side cover for wiring
2.
Select L and N wires as right
figure and table
3
below:
Cross Section
(mm
2
)
Maximum Length for 1% Loss (Meter)
SP5000 Vitality Eco
2.5
7
4
11
6
16
3.
Insert wires through bottom plate
4.
Crimp the wires with y-terminals
5.
Insert wires with terminals, fix them according to polarity and torque
on terminals as figure
6.
Fix wires with cable ties
Connecting AC Loads
1.
Prepare similar wires as AC mains
3
The table is based on 20°C environment, installer need to adjust according to application and
local regulation