5-9
Type (C-01).
The scan frequency is settable from 1 minute to 4 hours and the factory setting is
1 hour. Press the UP and DOWN key to increase or decrease the length of time.
P and O (Perturb and Observe) will run a full scan at the set time interval
(frequency) and then do P and O scans at shorter intervals in between.
Scan and Hold will run a full scan at the set time interval (frequency) and then
hold the resultant MP until the next interval. This is also settable from 1 minute
to 4 hours; factory is 1 hour.
C-03: Set Percentage VOC
This constant is only displayed if Percentage is selected as MPPT Type (C-01).
Percentage measures the VOC at the set time interval and calculates the
operating Vmp based on the percentage set. The percentage set point can be from
0 – 100% and factory setting is 80%.
C-04: Set Percentage EveryTime
This constant is only displayed if Percentage is selected as MPPT Type (C-01).
When Percentage measure the VOC, the time interval can be set and time is 1
minute to 4 hours. Factory setting is 1 hour.
C-05: Set Hold Input Volts
This constant is only displayed if Hold Input V is selected as MPPT Type (C-01).
Hold Input Voltage will regulate based on the input voltage set (0-140V) for
SC-80 MPPT and (0-240V) for SC-160X MPPT, based on the panel type. The
output current will be based on that voltage.
Group D
Auxiliary Relay 1
D-01: Set Aux Relay 1 Mode
The Auxiliary Relays are useful for functions such as turning a generator on or
off at low battery voltage or load change, turning on an external fan when battery
temperature increases, or shedding certain loads at specific times. Additional
Summary of Contents for SC-160X MPPT
Page 7: ...VII Dimension for SC 50 MPPT Unit mm Fig 1...
Page 8: ...VIII Dimension for SC 80 MPPT Dimension for SC 80X MPPT Unit mm Fig 2...
Page 9: ...IX Dimension for SC 160X MPPT Unit mm Fig 3...
Page 12: ...1 3 Fig 4...
Page 20: ...3 2 3 2 The following is the Initialization Stage Flow Chart OTPI Solar SC 80 MPPT V0 9311...
Page 27: ...3 9 Main Menu Programming Group F Menu Group Constants Constants Edit Data Enter...
Page 28: ...3 10 Main Menu Programming Group O Menu Group Constants Constants Edit Data Enter...
Page 29: ...3 11 Main Menu Data Log Menu Constants Constants Edit Data Enter...